3-4 Receiving & Installation
MN2412
Frame Ground Connection
Continued
Figure 3-3 Frame Ground Connection
Earth Ground
Frame
Stud
Washer
Ground Wire Lug
Nut
Washer
Engine Oil
Refer to the engine manual that was provided with your generator. Determine the correct type of
engine oil and the amount specified by the engine manufacturer. Add the required amount of oil
to bring the oil level to full.
Battery Connections
Applies to 12VDC Electric Start models only.
Note: PC90VE units that have an electronic governor must have a battery installed before the
Genset can be started (even with the pull starter). If no battery is present or the battery is
discharged, the electronic governor will not operate and the generator set will not run.
The generator is shipped with no battery installed.
WARNING: Do not dispose of battery or batteries in a fire. The battery is capable of exploding. If the
battery explodes, electrolyte solution will be released in all directions. Battery electrolyte
solution is caustic and can cause severe burns and blindness. If electrolyte contacts skin or
eyes, immediately flush the area with water and seek medical attention quickly.
WARNING: Do not mutilate the battery . The battery contains electrolyte solution which is caustic and
can cause severe burns and blindness. If electrolyte contacts skin or eyes, immediately flush
the area with water and seek medical attention quickly.
WARNING: A battery presents a risk of electrical shock hazard and high short circuit current. The
following precautions are to be followed when working on batteries:
1.
Remove watches, rings, necklaces and all other metal objects.
2.
Use tools with insulated handles.
3.
Wear rubber gloves and boots.
WARNING: The battery electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is
electrically conductive and corrosive. The following precautions are to be followed when
working on batteries:
1.
Wear full eye protection (safety glasses or goggles) and protective clothing.
2.
Where electrolyte contacts the skin, flush the area immediately with water and wash it
off using soap and water.
3.
Where electrolyte contacts the eyes, immediately flush the eye thoroughly with water
and seek medical attention quickly.
4.
Spilled electrolyte is to be washed down with an acid neutralizing agent. A common
practice is to use a solution of one pound (500 grams) bicarbonate of soda to one
gallon (four liters) of water. the bicarbonate solution is to be added until evidence of
reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the
area dried.
WARNING: A battery presents a risk of fire because they generate hydrogen gas. Hydrogen gas is
extremely explosive. Never jump start a battery, smoke in the area around the battery or
cause any spark to occur in the area around the battery. The following precautions are to be
followed when working on batteries:
1.
Do not smoke when near batteries.
2.
Do not cause flame or spark in battery area.
3.
Discharge static electricity from body before touching batteries by first touching a
grounded metal surface.
Summary of Contents for Powerchief PC Series
Page 1: ...PowerchiefR POW R Products Generator Series PC Installation Operating Manual 4 04 MN2412 ...
Page 4: ...ii Table of Contents MN2412 ...
Page 12: ...2 2 General Information MN2412 ...
Page 26: ...A 4 PowerchiefR Series MN2412 Figure A 5 PC30H Wiring Diagram ...
Page 27: ...PowerchiefR Series A 5 MN2412 Figure A 6 PC40H Wiring Diagram ...
Page 28: ...A 6 PowerchiefR Series MN2412 Figure A 7 PC50H Wiring Diagram ...
Page 29: ...PowerchiefR Series A 7 MN2412 Figure A 8 PC60H Wiring Diagram ...
Page 30: ...A 8 PowerchiefR Series MN2412 Figure A 9 PC90VE Wiring Diagram ...