Software Setup 5-5
Standard Series H Area Register Mapping
(except 15H and 21H controls)
Register
Address
T#
Read/Write
Description
48000
17
Read Only
Current Actual (100mA RMS)
48001
18
Read Only
Speed Actual (RPM)
48002
19
Read Only
Frequency Actual (.1 Hz)
48003
20
Read Only
Power Actual (Watts)
48004
21
Read Only
Input Voltage (Volts RMS)
48005
22
Read Only
Output Voltage (Volts RMS)
48006
24
Read Only
Motor Direction (0=fwd,1=rev)
48007
25
Read Only
Zero Speed (1=at zero)
48008
26
Read Only
At Speed (1=at commanded speed)
48009
27
Read Only
Warning (1=warning)
48010
28
Read Only
At Position (1=at position)
48011
29
Read Only
At Setpoint (1=at setpoint)
48012
30
Read Only
At Set Speed (1=at set speed)
48013
31
Read Only
Terminal Strip (see NOTE 1)
48014
71
Read Only
Analog Input 1
48015
72
Read Only
Analog Input 2
48016
73
Write Only
Analog Output 1
48017
74
Write Only
Analog Output 2
48018
75
Write Only
Digital Output
48019
33
Read Only
Software Revision
(ex S15–4.03 is returned as 403)
48020
34
Read Only
Product Series (ex Series 15H returns 15)
48021
35
Read Only
Product Class (5=H)
48022
36
Read Only
Option Id 1
48023
37
Read Only
Option Id 2
48024
38
Read Only
Run Time (low order)
48025
38
Read Only
Run Time (high order)