5-2 Software Setup
Action
Description
Display
Comments
Press
Y
or
B
key
Scroll to Serial mode
OPERATING MODE
SERIAL
Change to
Serial mode.
Press
Enter key
Saves mode change value
OPERATING MODE
P:
SERIAL
Press
Y
key
Scroll to Command Select
parameter
COMMAND SELECT
P:
+/–10VOLTS
Now in
±
10 Volt
input mode.
Press
Enter key
Flashing cursor indicates
mode can be changed
COMMAND SELECT
+/–10VOLTS
Press
Y
or
B
key
Scroll to Serial mode
COMMAND SELECT
SERIAL
Change to
Serial mode.
Press
Enter key
Saves change to serial
command select
COMMAND SELECT
P:
SERIAL
Control is now
in Serial mode.
Press
Y
or
B
key
Scroll to Level 2 blocks
PRESS ENTER FOR
LEVEL 2 BLOCKS
Press
ENTER
key
Select Level 2 blocks.
PRESS ENTER FOR
OUTPUT LIMITS
First screen in
Level 2 block
Press
Y
or
B
key
Scroll to Communications
block
PRESS ENTER FOR
COMMUNICATIONS
Press
ENTER
key
Select Level 2
Communications block.
PROTOCOL
p:
RS232 ASCII
Press
Enter key
Flashing cursor indicates
mode can be changed
PROTOCOL
RS232ASCII
Press
Y
or
B
key
Scroll to RS 485 BBP
(Baldor Binary Protocol)
PROTOCOL
RS485BBP
Press
ENTER
key
Select RS 485 BBP mode.
PROTOCOL
p:
RS485BBP
Press
Y
or
B
key
Scroll to Exit Menu
PRESS ENTER FOR
MENU EXIT
Press
DISP key
Returns to Display mode.
STP MOTOR SPEED
LOCAL
0RPM
Display mode.
Press
LOCAL
key
Changes to Serial
Operation.
STP MOTOR SPEED
SERIAL
0RPM
Ready for
Modbus Plus
operation.
Note: The 15H control does not have a Command Select “Serial”,
this is not needed for this control.
The control is now configured for Modbus Plus mode and the Host
software can now be setup.