ES-787 Rev E
Page 3 of 6
{Intrinsically Safe}
IS CL I, II, III; DIV 1; GP A, B, C, D, E, F, G
{Non-Incendive, gas}
NI CL I; DIV 2; GP A, B, C, D
{Suitable for dust & fibers,Div 2}
SUITABLE FOR CL II, III; DIV 2; GP F, G
{Explosionproof, gas}
XP CL I; DIV 1 GP B, C, D
{Suitable for dust, Div 1}
SUITABLE FOR CL II; DIV 1; GP E, F, G
{Suitable for fibers,Div 1}
SUITABLE FOR CL III, DIV 1
T5 Ta=85°C T6 Ta=75°C
(ATEX)
AT EX S P ECIFIC N O T E:
PERMANENTLY MARK THE PROTECTION TYPE CHOSEN. ONCE THE TYPE HAS BEEN MARKED, IT CAN NOT BE CHANGED
Certificate Number -
FM11ATEX0008X
{Intrinsically Safe, gas}
II 1G Ex ia IIC T6…T5 Ga
{Intrinsically Safe, dust}
II 1D Ex ia IIIC T96°C Da
Certificate Number -
FM06ATEX0004X
{FlameProof, gas}
II 2G Ex db IIB+H2 T6…T5 Gb
{FlameProof, dust}
II 2D Ex tb IIIC T96°C Db
Certificate Number -
FM06ATEX0005X
{Limited Energy, gas}
II 3G Ex ic IIC T6…T5 Gc
{Limited Energy, dust}
II 3D Ex tc IIIC T96°C Dc
O peratingR anges
5.5.1
Ambient Temperature: -50°C to +85°C
5.5.2
Electrical:
30 VDC Max,
1 Watt Max
Ui=6.5 Volts
li=10.5mA
Ci=0.066µF
Li=0
Pi=68mW
AP P R O VED