SPECIAL INSTRUCTIONS FOR INSTALLING THE MASONEILAN

“SVI-II REMOTE MOUNT” IN AREAS WHERE THERE IS A POTENTIAL FOR EXPLOSIVE GAS ATMOSPHERE OR INFLAMMABLE DUST

Page 1 of 6

Drawn

P. Morley

4APR14

Approved

H. Smart

4APR14

ES-787

F

REV

Description

Date

A

Initial Release

May 2014

B

PDR ECO-0026891

Oct 28, 2016

C

PDR ECO-0029101

May 16, 2017

D

PDR ECO-0033385

May 1, 2018

E

PDR ECO-0042635

Oct 29, 2020

F

PDR ECO-0043755

Feb 2, 2021

1

IN T R O DU CT IO N

This manual covers the requirements for safe installation, repair, and operation of the SVI-II REMOTE MOUNT as it relates to operation in areas
where there is a potential for explosive atmosphere or inflammable dust. Adherence to these requirements assures that the SVI-II REMOTE will
not cause ignition of the surrounding atmosphere. Hazards related to control of the process are beyond the scope of this manual.

For mechanical mounting instructions on specific valves/actuators refer to the mounting instructions supplied with the corresponding mounting kit.
Mounting does not affect the suitability of the SVI-II REMOTE MOUNT for use in a potentially hazardous environment.

The SVI-II REMOTE MOUNT is manufactured by:

Dresser LLC
12970 Normandy Blvd.
Jacksonville FL – 32221 – USA

For language translation assistance, contact your local representative or e-mail

[email protected]

.

Pour la langue de traduction aide, contactez votre représentant local ou envoyez un e-mail

[email protected]

.

2

GEN ER AL R EQ U IR EM EN T S

Installation and maintenance must be performed only by qualified personnel. Area Classification, Protection Type, Temperature Class, Gas Group,
and Ingress protection must conform to the data indicated on the label.

Wiring and conduit must conform to all local and national codes governing the installation. Wiring must be rated for at least 5ºC above the highest
expected ambient temperature.

Approved wire seals against ingress of water and dust are required and the NPT fittings must be sealed with tape or thread sealant in order to
meet the highest level of ingress protection.

Where the protection type depends on wiring glands, the glands must be certified for the type of protection required.

The metal housing is a die-casting alloy which is predominately aluminum.

Before powering the SVI-II REMOTE MOUNT:

Verify that the cover is fully threaded onto the housing such that the two crescent-shaped bosses are aligned and approximately in contact. Then
thread the supplied M8 socket-head cap screw securely into the threaded hole d (This ensures that the cover is not inadvertently removed). This
can be seen in the image below.

M8 Socket-Head Cap Screw

!WARNING!
Failure to adhere to the requirements listed in this manual may cause loss of life
and property.

Original instructions