4. Optional Find Stops and Open Stops Adjustments
1. Click
Calibration > Find Stops
and the tab appears (Figure 10). Click
Auto Stop Limit
and
then
Start
. If the attempt is:
Successful, skip to “5. Perform Autotune” on page 14.
Not successful, read the
Find Stops Log
. Note the reasons for failure. If magnets are out
of range, then:
a. Click
Find Stops
tab.
b. Adjust the magnet noting
Raw Sensor Value
and picture of magnets.
Figure 10 Find Stops
2. For ATO actuator, perform an Open Stop Adjustment by:
Use mechanical means, if available on the valve, to restrict the
stops. If not available, use the Masoneilan software.
Red line indicates failure.
Yellow line indicates warning.
NOTE