background image

4  |  Baker Hughes

Copyright 2020 Baker Hughes Company. All rights reserved.

1. General 

These  adjustment  and  maintenance  instructions  apply  to  the 

10900 Series Actuators used with the Masoneilan 500 Series 

Pressure  Regulators.  They  include  a  parts  reference  list 

including recommended spare parts.
For installation, operation, adjustment and maintenance of the 

500 Series Regulators body S/A refer to instructions numbers 

indicated by the following table.

Regulator

Model No

525;    525-50

526;    526-50

Body S/A

Instruction No

535H;    535H-50

536H;    536H-50

535V;    535V-50

30557

31597

176419 E

Spare parts

When  performing  maintenance  always  use  Baker  Hughes 

 

replacement  parts.  Masoneilan  Parts  are  obtainable  through 

your local Baker Hughes Representative or Masoneilan Spare 

Parts  Department.  When  ordering  parts,  always  include 

Masoneilan Model and Serial Numbers shown on serial plate.

After sales Department

Baker  Hughes  has  a  highly  skilled  After  Sales  Department 

available for start-up, maintenance and repair of our regulators and 

 

components  parts.  Contact  the  nearest  Baker  Hughes  Sales 

Office or Representative.

Training

Baker  Hughes  Masoneilan  regularly  holds  training  seminars 

for technicians. In order to participate in one of these training 

seminars you should contact our local Baker Hughes Masoneilan 

Representative or our Training Department.

The following instructions should be thoroughly 

reviewed and understood prior to installing operating 

or performing maintenance on this equipment. Only

 

qualified personnel to service this equipment.

Non-compliance with safety rules and caution notes 

of this instruction may bring about malfunction of 

the device or damage it seriously. In addition, such 

negligence might expose personnel present in the field 

to grave hazards.

2. Description-Operation 

The 10900 Actuator is a simple powerful mechanical device. It 

is Air-to-Extend Stem type. The nominal range of an actuator is 

the pressure range in pounds per square inch (psi) in which the 

 

pressure setting can be obtained by adjustment.
Conformation of the diaphragm (11) to the diaphragm plate (10) 

serves as a flexible upper guide for the actuator stem (6). Nylon 

reinforced  neoprene  diaphragms  permit  smooth,  sensitive 

 

operation. The lower guide is an oil impregnated bronze bush-

ing (3) located in the spring adjuster (2).

Note:

 On request, for special services, the nylon reinforced  

neoprene diaphragm may be provided with a PTFE coating. 

Other materials are optional and available to suit the fluids 

involved.

Regulator

Model No

REDUCING

Function

Spring Diaphragm

Actuator Type

525

535H

535V

BACK

PRESSURE

DIFFERENTIAL

REDUCING

525-50

535H-50

535V-50

526

536H

Differential

526-50

536H-50

DIFFERENTIAL

BACK PRESSURE

The 10900 Series Actuators are designed for use with the 500 

Series Regulators for reducing, back pressure and differential 

pressure applications.
The  opposite  chart  indicates  the  combinations  available  to 

 

provide the desired function. The 10900 Series Actuators are 

 

designated by the nominal range (psi). See the following chart.
In  Spring  Diaphragm  Actuators,  three  actuator  cases  are 

 

available: a case rated for 60 psi static pressure, a case rated 

for 250 psi static pressure and a case rated for 750 psi static 

 

pressure.
In  Differential  Pressure  Actuators,  two  actuator  cases  are 

 

available: a low-pressure case rated for 250 psi static pressure, 

and a high-pressure case rated at 600, 1000 and 1500 psi static 

pressure.

Range

(psi)

Actuator

Type

0.5 - 3

Max. Static

Pressure

(psi)

Case

Size

2 - 10

6 - 20

15 - 40

30 - 75

60 - 125

80 - 250

150 - 750

3 - 12

10 - 35

30 - 75

60 - 125

3 - 15

30 - 85

5 - 30

10 - 60

75 - 185

L o w   P r e s s u r e   C a s e

Spring

Diaphragm

Differential

H i g h   P r e s s u r e   C a s e

100 - 330

250

600

1000

1500

5

4

5

4

3 1/2

5

9

4

3 1/2

Special

60

250

750

Summary of Contents for Masoneilan 10900 Series

Page 1: ...Baker Hughes Data Classification Public Masoneilan 10900 Series Spring Diaphragm and Differential Pressure Actuators for use with 500 Series Regulators Instruction Manual Rev D ...

Page 2: ...ICULAR REQUIREMENTS FOR OPERATION OF OTHER EQUIPMENT AT THE SITE THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT NOR TO PROVIDE FOR EVERY POSSIBLE CONTINGENCY TO BE MET IN CONNECTION WITH INSTALLATION OPERATION OR MAINTENANCE SHOULD FURTHER INFORMATION BE DESIRED OR SHOULD PARTICULAR PROBLEMS ARISE WHICH ARE NOT COVERED SUFFICIENTLY FOR THE CUSTOMER OPERATOR S PUR...

Page 3: ...all not be transcribed or copied without Baker Hughes s written permission Please report any errors or questions about the information in this manual to your local supplier These instructions are written specifically for the 10900 Series Actuators and do not apply for other valves outside of this product line Useful Period The current estimated useful life period for the 10900 Series Actuators is ...

Page 4: ...iption Operation The 10900 Actuator is a simple powerful mechanical device It is Air to Extend Stem type The nominal range of an actuator is the pressure range in pounds per square inch psi in which the pressure setting can be obtained by adjustment Conformation of the diaphragm 11 to the diaphragm plate 10 serves as a flexible upper guide for the actuator stem 6 Nylon reinforced neoprene diaphrag...

Page 5: ...ing Adjuster 3 Bushing Incl Ref 2 4 Lower Spring Seat 5 Actuator Spring 6 Actuator Stem 7 Cap Screw L case to yoke 8 Diaphragm Case Lower 9 2 Diaphragm Chamber 10 Diaphragm Plate 11 Diaphragm 13 Diaphragm Case Upper 14 1 Diaphragm Washer 15 Cap Screw Diaph case 16 Nut Diaph case 17 2 Stud Diaph case 18 Stop Cup 21 4 Reducing Ring 22 5 Stop Screw 23 5 Stop Spacer 27 1 Upper Spring Washer 28 1 Lockn...

Page 6: ...3 O Ring 26 O Ring Retainer 27 Upper Spring Seat Incl w Ref 6 28 1 Locknut 29 1 Connection Adapter Ref Part Name Ref Part Name Ref Part Name Recommended spare parts 1 Only on Low Pressure Case Design 2 Only on High Pressure Case Design 3 Qty 2 on Low Pressure Case Design Qty 1 on High Pressure Case Design 3 Installation On steam service the regulator should be installed with the actuator down so t...

Page 7: ...ote By means of a wrench applied on the plug stem nuts hold the actuator stem during this operation Install new diaphragm and reassemble by reversing of the above description order Readjust the spring compression see above On Differential Actuators 500 50 Series Regulators Figure 2 a On low pressure case design Remove the high and low pressure lines from the diaphragm case 13 and the diaphragm cha...

Page 8: ...mation The Baker Hughes logo and Masoneilan are trademarks of Baker Hughes Company Other company names and product names used in this document are the registered trademarks or trademarks of their respective owners BHMN 10900 IOM 31593D 0720 07 2020 Direct Sales Office Locations Find the nearest local Channel Partner in your area valves bakerhughes com contact us valves bakerhughes com Australia Br...

Reviews: