TROUBLESHOOTING
INTRODUCTION
I-E96-203C
5 - 3
35
0 0 1 1 0 1 0 1
Internal error - spurious/
unassigned exception
Reset MFP module. If error recurs, replace
MFP module.
36
0 0 1 1 0 1 1 0
Internal error - divide by 0 or
check instruction
37
0 0 1 1 0 1 1 1
Internal error - undefined trap
Restart MFP module. If error recurs, replace
MFP module.
38
0 0 1 1 1 0 0 0
Board level hardware error
Contact Bailey field service.
3F
0 0 1 1 1 1 1 1
Normal stop
None.
40
0 1 0 0 0 0 0 0
Backup - cold takeover ready
80
1 0 0 0 0 0 0 0
Backup - hot takeover ready
C0
1 1 0 0 0 0 0 0
Primary - operating
XX
1
—
Unknown
Contact Bailey field service.
NOTE:
1. This symbol represents any LED combination not specifically addressed in this table.
Table 5-2. Other MFP Module Conditions
LED
Condition
Corrective Action
Status
Off
Check power.
Check module seating.
Check jumper J4. Remove if installed.
If power and seating are okay, remove the module
and replace with identically configured module.
Red
Press reset button. If LED remains red, remove the
module and replace with identically configured
module.
Green
None - normal.
Orange
Remove jumper J4.
Group B
7/8
Off
Check power.
Check module seating.
If power and seating are okay, remove the module
and replace with identically configured module.
Red
None - indicates primary module.
Group B
8
Off
Check power.
Check module seating.
If power and seating are okay, remove the module
and replace with identically configured module.
Red
None - indicates backup module in redundant
configuration.
Table 5-1. IMMFP03 Error Codes
(continued)
Code
LED
8 7 6 5 4 3 2 1
Condition
Corrective Action