INSTALLATION
INSTALLING THE TERMINATION MODULE
2 - 4
I-E96-408A
®
INSTALLING THE TERMINATION MODULE
If the fuse and jumpers are in place, the termination module is
ready to install.
Installing the Termination Module Cables
Before mounting the termination module in the TMU, install
the termination cables. Table
lists the cables, their applica-
tion, connector assignments and length restrictions. Figures
and
show diagrams of cable connections to the LIM
and NIS. To install the termination module cable:
1. Install the hooded end of the appropriate cable in the mod-
ule mounting unit (MMU) backplane slot assigned to the LIM or
NIS. Because of keyed connectors on the termination cable, it
should easily snap into place when properly installed.
NOTE: If the LIM or NIS module is installed, pull the module away
from the MMU backplane several inches. The card edge of the mod-
ule must not come into contact with the card edge connector of the
termination cable while installing the cable. After installing the cable,
slide the module into the MMU so that the card edge sits within the
card edge connector. Refer to the product instructions for the
INLIM03 or INNIS01 for more information about the installation or
removal of those modules.
2. Install the other end of the termination cable in the termi-
nation mounting unit (TMU) backplane slot assigned to the
ICL. Because of keyed connectors on the termination cable, it
should easily snap into place when properly installed.
Mounting the Termination Module
The termination module occupies one slot in the INFI 90 termi-
nation mounting unit.
NOTE: You can install the communication cable before or after mount-
ing the TM. It may be easier for you to install the communication cable
with the board lying on a flat work surface (near the cabinet). If so,
install the cable before mounting it by following the steps under Com-
munication Cable Installation. To mount the termination module:
1. Locate the slot in the TMU that is assigned to the ICL.
2. Inserting the TM card edge first, align the termination mod-
ule with the guide rails in the TMU.
3. Slide the module into its slot. If the communication cable
and power wiring have been installed, fully insert the TM until
it seats in the cable connector at the rear of the TMU.
4. Snap on the front cover of the termination module.