INTRODUCTION
NOMENCLATURE
1 - 4
I-E96-434A
®
NOMENCLATURE
contains the modules and equipment that can be
used with the NIAI02 module:
SPECIFICATIONS
Refer to Table
for the specifications of the NIAI02 Termina-
tion Unit.
Table 1-3. Nomenclature
Nomenclature
Description
IMASM02
Thermocouple and Millivolt Input Slave Module
NIAC02
Thermocouple Calibration Module
NIAM02
Analog Master Termination Module
NKTM01
Cable, Termination Module (Ribbon)
NKTU02
Cable, Termination Module (PVC)
NKTU12
Cable, Termination Module (non-PVC)
258436A1
Cable retaining kit used when a round cable connects
to the TMU
NTMU01
Termination Mounting Unit (Rear Mount)
NTMU02
Termination Mounting Unit (Front Mount)
Table 1-4. Specifications
Property
Characteristic/Value
Power Requirements
24 VDC at 10 mA.
Mounting
Slides into a single slot in the termination mounting unit NTMU01/02.
Environmental
Electromagnetic/
Radio Frequency Interference
No values available at this time. Keep cabinet doors closed. Do not use
communication equipment closer than 2 meters from the cabinet.
Ambient Temperature
0 to 70
o
C (32 to 158
o
F)
Relative Humidity
5% to 90%
±
5% up to 55
o
C (131
o
F) (noncondensing).
5% to 40%
±
5% up to 70
o
C (158
o
F) (noncondensing).
Atmospheric Pressure
Sea level to 3 km (1.86 miles).
Air Quality
Noncorrosive.
Cooling Requirements
No cooling is necessary when used in Bailey Controls cabinets and
operated within stated limits.
Surge Protection
Meets IEEE-472-1974 Surge Withstand Capability Test
1
.
Certification
CSA certified for use as process control equipment in an ordinary (non-
hazardous) location.
NOTE: 1. Do not use the NKTM01 cable when compliance with IEEE-472-1974 is necessary.
Specifications are subject to change without notice.