![Bailey Infi 90 NIAC04 Instruction Download Page 21](http://html1.mh-extra.com/html/bailey/infi-90-niac04/infi-90-niac04_instruction_3500321021.webp)
INTRODUCTION
I-E96-421A
A - 1
APPENDIX A - IMASM04 ANALOG SLAVE INPUT MODULE
INTRODUCTION
The IMASM04 Analog Slave Module uses a NIAC04 module to
calibrate the RTD inputs. This appendix contains a figure and
table that shows the dipswitch location on the IMASM04 mod-
ule and its settings. This information is provided as a quick ref-
erence guide for personnel installing the NIAC04 module.
Figure
shows the IMASM04 module address select switch
(SW1). Table
lists the binary addresses for setting SW1.
Refer to the IMAMM03 instruction for more detailed informa-
tion to install and configure the slave.
Figure A-1. Address Select Switch (SW1)
T00467A
P2
P3
P1
MODULE
STATUS LED
SLAVE ADDRESS
SWITCH
S1
2
1
OPEN
3
Table A-1. Address Switch Settings (SW1)
Address
MSB
Pole 1
Pole 2
LSB
Pole 3
Address
MSB
Pole 1
Pole 2
LSB
Pole 3
0
0
0
0
4
1
0
0
1
0
0
1
5
1
0
1
2
0
1
0
6
1
1
0
3
0
1
1
7
1
1
1
NOTE: OPEN = OFF = 1; CLOSED = ON = 0