INSTALLATION
UNPACKING AND INSPECTION
2 - 2
I-E96-421A
®
UNPACKING AND INSPECTION
These are steps to follow for general handling:
1. Examine the module to make sure that no damage has
occurred in transit.
2. Notify the nearest Bailey Controls sales office of any dam-
age.
3. File a claim for any damage with the shipping company
that handled the shipment.
4. Use the original packing material or container to store the
module.
5. Store the module in a place with clean air; free of extremes
of temperature and humidity.
SET UP/PHYSICAL INSTALLATION
This section explains how to configure and install the NIAC04
module. The required procedures are installing the module into
the TMU card rack and connecting the cable.
Jumper Settings
There are eight jumpers on the NIAC04 module, one for each
input. Each jumper selects zero or span for its respective
input. The IMAMM03 master module issues the calibration
commands to the IMASM04 slave module being calibrated. To
calibrate the zero, place the jumper over the lower and middle
pins on the input being calibrated. To calibrate the span, place
the jumper over the upper and middle pins on the input being
calibrated. Zero and span must be calibrated separately for
each input. Refer to the IMAMM03 module product instruction
for calibration instructions. Figure
shows the calibration
jumper locations on the NIAC04 circuit board.
Cable Installation
The NKTU02, NKTU12, or NKTM01 cable connects the NIAC04
module to the IMASM04 module. Locate the slave calibration
slot as close as possible to the master module. The NKTM01
cable is a flat ribbon cable. The NKTU02 cable is a round,
shielded cable with PVC jacket. The NKTU12 module is a
round, shielded cable with nonPVC jacket.
Figure
shows the cabling from the NIAC04 module to the
IMASM04 module. Table
lists the NIAC04 module cable
connections.