INSTALLATION
INBTM01 SWITCH SETTINGS
I-E96-621A
3 - 7
INBTM01 SWITCH SETTINGS
The Bus Transfer Module (INBTM01), shown in Figure
, has
one user-configured dipswitch (SW1). SW1 enables module
diagnostics. Refer to Table
and set SW1 for normal
operation.
Figure 3-3. BTM Switch (SW1) Location
Table 3-7. BTM Options (SW1)
Switch Position
Function
User Setting
1
2
3
4
5
0
0
0
0
0
Normal operation.
0
0
0
1
0
Normal BTM operation without catastrophic error checking (for
Test Purposes ONLY).
0
0
1
0
0
RAM test mode. If Status LED turns red, the module has failed
the test.
0
0
1
1
0
ROM test mode. If Status LED turns red, the module has
failed the test.
0
1
0
0
0
Execute Interrupt Request (IRQ) LIM handshake diagnostic.
Used in combination with the LIM off-line diagnostics.
0 = Closed (on)
1 = Open (off)
T00401A
RESET
SWITCH
SW1
OPTION SWITCH
EDGE
CONNECTORS
P3
P2
P1
5
1
OPEN