INSTALLATION
INNPM11 NETWORK PROCESSING MODULE CONFIGURATION
3 - 10
WBPEEUI250016A1
®
Dipswitch SW4 - Options
Dipswitch SW4 is an eight-pole dipswitch that sets the operat-
ing options of the NPM module. Refer to Table
for option
settings. Record the dipswitch SW4 settings in the space
provided.
4 - 7
0
Unused.
8
4
1
Controlway module address one.
0
Controlway module address zero.
NOTES:
1. 1 = OPEN or OFF, 0 = CLOSED or ON.
2. Shaded areas designate normal operating positions.
3. To operate in Controlway mode all modules must be operating in the Controlway mode
4. Each NPM module of a redundant pair must have a unique address.
Table 3-7. INNPM11 Module Dipswitch SW3 Settings
(continued)
Pole
Setting
1,2
Function
2
User
Setting
Table 3-8. INNPM11 Module Dipswitch SW4 Settings
Pole
Setting
1,2
Function
2
User
Setting
1
1
ROM checksumming disabled.
0
ROM checksumming enabled.
2
1
Failover on power system status failure enabled.
0
Failover on power system status failure disabled.
3
1
Redundant module expected.
0
Redundant module not expected.
4
3
1
INFI-NET diagnostics enabled.
0
INFI-NET diagnostics disabled.
5/6
0/0
Exception report poll rate: 1 poll per second (slow).
0/1
Exception report poll rate: 2 polls per second (slow).
1/0
Exception report poll rate: 4 polls per second (standard).
1/1
Exception report poll rate: 8 polls per second (fast).
7
1
Test mode enabled.
0
Test mode disabled.
8
0
Unused.
NOTES:
1. 1 = OPEN or OFF, 0 = CLOSED or ON.
2. Shaded areas designate normal operating positions.