NICL01 TERMINATION MODULE CONFIGURATION
INTRODUCTION
WBPEEUI250016A1
B
-
3
Figure B-4. Redundant Process Control Unit Interface NICL01 Connections
P R IM A RY
IN N IS 01
P1
P1
P1
P1
P3
P3
P3
P3
P2
P2
P2
P2
P R IM A RY
IN N P M ? 1
B AC K U P
IN N P M ? 1
B AC K U P
IN N IS 01
N K L S0 1/1 1
N K L S0 1/1 1
L O O P W IR IN G
N IC L0 1
N IC L0 1
TB1
TB1
TB2
TB2
TB3
TB3
TB4
TB4
IN
LOO P 1
OU T
IN
LOO P 1
OU T
IN
LOO P 2
OU T
IN
LOO P 2
OU T
TB5
TB5
J4
J4
J3
J3
J2
J2
J1
J1
P 1
P 1
L O O P W IR IN G
L O O P
W IR IN G
I/O
E XPA N D E R
BU S
I/O
E XPA N D E R
BU S
N K M P0 1 /1 1
N O T E: L O O P W IR IN G C AN
B E C O A X IAL O R T W IN A X IA L .
T 01 7 53 A
Table B-1. NICL01 Jumper Settings for Revision C
Jumper Number
Jumper Settings
Twinaxial Cable
Coaxial Cable
J5 - J12
2-3
2-3
J13 - J18
1-2
2-3
Table B-2. NICL01 Jumper Settings for Revision D or Greater
Jumper Number
Jumper Settings
Twinaxial Cable
Coaxial Cable
J5 - J10
1-2
2-3