INSTALLATION
INNIS01 NETWORK INTERFACE SLAVE MODULE CONFIGURATION
3 - 6
I-E96-613A
®
Figure 3-2. Dipswitch SW4
Pole Assignments
Table 3-4. INNIS01 Address Settings
Address
Example
Dipswitch Pole
(Binary Value)
1
2
3
(4)
(2)
(1)
0
0
0
0
3
0
1
1
7
1
1
1
User setting
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
I/O EXPANDER
BUS ADDRESS OF
INNIS01 MODULE
EVENT AND ERROR
COUNTER SETTING
TP21197A
1
2
3
4
OPEN
5
6
7
8
Table 3-5. INNIS01 Event Counters
Dipswitch Pole
1,2
(Binary Value)
Hexadecimal
Value
2
Description
2
4
5
6
7
8
(16) (8)
(4)
(2)
(1)
0
0
0
0
0
00
No. of timer interrupts.
0
1
0
0
1
09
No. of multicast messages received (excluding originated
messages).
0
1
0
1
0
0A
No. of multicast destinations received.
0
1
0
1
1
0B
No. of time sync messages received (excluding origi-
nated messages).
0
1
1
0
0
0C
No. of broadcast messages received (excluding origi-
nated messages).
0
1
1
0
1
0D
No. of NIS poll messages received (excluding originated
messages).
0
1
1
1
0
0E
No. of poll messages acknowledged by this node.
0
1
1
1
1
0F
No. of poll messages busy-negative acknowledged by
this node.
1
0
0
0
0
10
No. of messages transmitted (total loop traffic).
1
0
0
0
1
11
No. of loop messages received and forwarded by this
node.
1
0
0
1
0
12
No. of messages originated by this node (including
retries).