INSTALLATION
INNIS01 NETWORK INTERFACE SLAVE MODULE CONFIGURATION
I-E96-613A
3 - 3
Dipswitch Settings
There are four dipswitches on the NIS module. The dipswitches
and their functions are described below. See Figure
for
dipswitch locations.
DIPSWITCH SW1 - NODE ADDRESS
This dipswitch sets the node address. Valid INFI-NET node
addresses are one through 250. Valid Plant Loop node
addresses are one through 63 (refer to Table
). Pole one is
the most significant bit with a binary weight of 128. Pole eight
is the least significant bit with a binary weight of one. Record
the dipswitch SW1 settings in the space provided.
Figure 3-1. INNIS01 Dipswitch and Jumper Locations
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4 5 6 7 8
OPEN
1 2 3 4 5 6 7 8
OPEN
1 2 3 4 5 6 7 8
OPEN
1 2 3 4 5 6 7 8
OPEN
SW4
I/O EXPANDER
BUS ADDRESS
SW3
LOOP MODE
SW2
LOOP ADDRESS
SW1
NODE ADDRESS
TP50144C
USER-CONFIGURED JUMPERS J1-J6
P1
P3
P2
J3
J6
J4
J1
J5
J2
GROUP A
LEDs
GROUP B
LEDs
Table 3-1. INNIS01 Dipswitch SW1 Settings
Node
Address
Example
Dipswitch Pole
(Binary Value)
1
2
3
4
5
6
7
8
(128) (64) (32) (16) (8)
(4)
(2)
(1)
1
0
0
0
0
0
0
0
1
63
0
0
1
1
1
1
1
1
250
1
1
1
1
1
0
1
0
User setting
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.