TROUBLESHOOTING
5 - 8
I-E96-225A
®
If pole 1 on SW2 is OFF, a running tally of successes and fail-
ures will be displayed on the LEDs. LEDs 1 through 4 tally the
passes, LEDs 5 through 8 tally the failures.
If a test fails with halt on error selected (SW2, pole 2 OFF), the
status LED turns red one second after the test status is dis-
played.
For the group test (10), each individual test is run in numerical
order. Upon failure, the test number that failed is displayed
when the test number display mode is selected. A failure of a
test within the group terminates the group test at that point.
All tests after the failing test in the group will not be run until
the fault is removed.
Figure 5-2. LEDs - Pass or Fail
TP 3 6 0 6 3 A
T E S T N U M B E R
M O D E FA IL
T E S T N U M B E R
FA IL / PA S S M O D E
FA IL U R E C O U N T
FA IL / PA S S M O D E
PA S S C O U N T
N O T U S E D
1
2
3
4
5
6
7
8
L S B
M S B
L S B
M S B
1
2
3
4
5
6
7
8
D IP S W IT C H S W 3
P O L E 1 O N
P O L E 1 O F F
L E D s
L E D s