INSTALLATION
I-E96-225A
3 - 9
Dipswitch SW3 - Normal Operation Mode
Dipswitch SW3 sets the IMCPM03 operation mode (normal or
diagnostics), the communication mode (Controlway or module
bus), and the module address (SPM/CPM02 mode or database
mode). Refer to Figure
for the dipswitch location.
In SPM/CPM02 and database modes, dipswitch SW3 provides
the following functions:
•
One pole to put the module in either diagnostic or normal
operation mode.
•
One pole to enable or disable the on-line ROM checksum
verification.
NOTE: On-line ROM checksum verification is always used for nor-
mal operation. It should not be disabled.
•
One pole to select Controlway or module bus mode.
•
Five poles to select the module address for SPM/CPM02
mode.
- or -
One pole to select the module address for database mode.
When the IMCPM03 module is operating in the SPM/CPM02
mode, the module can have an address from 0 through 31.
DB-25 computer port baud rate
and DB-9 EWS port baud rate
3
Computer
EWS
19200
1200
19200
2400
19200
9600
1200
1200
2400
2400
9600
2400
9600
9600
19200
19200
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
NOTES:
1. Bold values indicate default settings.
2. 0 = CLOSED or ON, 1 = OPEN or OFF.
3. The baud rate is determined by the device connected to the port.
Table 3-1. Dipswitch SW2 Option Settings
for Normal Mode
(continued)
Option
1
SW2 Pole Settings
2
1
2
3
4
5
6
7
8