INSTALLATION
DIPSWITCHES AND JUMPERS
3 - 4
I-E96-221A
®
•
One pole to enable the data base commands (available in
in software release B_0 or later of the IMCPM02 module).
•
One pole to enable the command/reply checksums for the
EWS port.
•
Two poles to select stop bits and parity bits for the EWS
port.
•
Three poles to select the baud rate for the EWS port..
Switch SW3 - Module Address
Dipswitch SW3 sets the IMCPM02 module address on Control-
way or module bus. The IMCPM02 module can have an
address from 0 through 31.
NOTE: If a CTT terminal is used, set the CTT terminal and the
IMCPM02 module to the same module address to avoid duplicate
address conflicts with the other modules of the process control unit.
Table 3-1. Dipswitch SW2 Settings for Normal Mode
Indicates default settings
Pole
Function
Settings
1
LED display
0 = EWS activity
1 = CTT activity
2
Data base commands
0 = Disabled
1 = Enabled
3
Command/reply checksums
0 = Disabled
1 = Enabled
4,5
EWS port characteristics
6, 7, 8
EWS port baud rate
NOTE: Open = OFF = Logic 1; closed = ON = Logic 0.
Setting
Parity
Stop Bits
0 0
None
1
0 1
Even
1
1 0
Odd
1
1 1
None
2
Setting
Baud Rate
0 0 0
0 0 1
150
300
0 1 0
0 1 1
600
1200
1 0 0
1 0 1
2400
4800
1 1 0
1 1 1
9600
19200