TROUBLESHOOTING
PROBLEM REPORTS
6 - 2
I-E96-301B
®
Function codes 215 and 216 generate five kinds of error
messages.
•
No response/wrong type (error type 1).
•
Calibration error (error type 2).
•
Channel failure/out of range (error type 3).
•
Calibration (error type 14).
•
Configuration mismatch (error type 7).
Problem reports are generated in response to three types of
errors detected by the function codes.
•
For a communication failure, if any message read by the
MFP from the IMASI03 fails.
•
If the detailed module status read from the IMASI03 by the
MFP indicates any error conditions.
•
If the channel status for any configured channel indicates
an error.
Table
contains the error types generated for each error.
Table 6-1. IMASI03 Error Types
Module Problem Report Type 12
Error
Type
Error Description
Slave Error
Corrective Actions
14
Calibration (0EH) problem
report (from FC 216)
Channel 1-16 Disabled Remove IMASI03 and insert. If error
recurs, replace the IMASI03.
14
Calibration (0EH) problem
report (from FC 215)
Cold Junction Disabled
14
Calibration (0EH) problem
report (from FC 216)
Channel 1-16 Not
Calibrated
14
Calibration (0EH) problem
report (from FC 215)
Cold Junction Not
Calibrated
7
1
Configuration Mismatch
problem report (from FC 216)
Channel Not
Configured
Verify that Specs 3 through 9 of the
indicated FC 216 are correct.
3
Channel Failure/Out of Range
(03H) problem report (from
FC 216)
Channel 1-16 Out Of
Range Error
Possible open input or signal is out of
range. Verify field wiring, connections,
sensor and module seating.
3
Channel Failure/Out of Range
(03H) problem report (from FC
215)
Cold Junction Out of
Range Error