background image

 

M-Bus AMR Interface E350 

User Manual

 

Page 5 from 6 

E111306819090 

Baer Energie- & Messtechnik GmbH 

 Siemensstr. 3 

 D-90766 Fürth 

 Phone +49 911 970590 

 Fax +49 911 9705950 

 

 

Technical data: 

Housing: 

Polycarbonate housing with terminals for using with Gyr E350 
meters (L+G ZxF domestic meters) 

Degree of protection: 

IP52 (according to IEC 60529) 

Protection class: 

Dimensions: 

165mm x 90mm x 33mm (W x H x D) 

Nominal voltage: 

230VAC (-20% / +15%) / 50Hz 
connection spring for one phase: Live (L1) and Neutral (N) from meter 

Power consumption: 

ca. 2,8W 

Temperature range: 

-45°C to +65°C (operational) 
-45°C to +90°C (storage temperature) 

LED displays: 

2 LED

’s:  

 

green:  

Power 

 

 

red:  

Error 

 

Interface: 

M-Bus (2 wires, passive) according to EN 13757-2 (physical layer)  

Baud rate: 

2400, 4800 or 9600 baud; default: 9600 baud (fixed baud rate) 

Data format: 

7E1, 8N1, 8E1; default: 7E1 

Transmission protocol: 

IEC 62056-21 (conform to VDEW2+) with fixed baud rate (OBIS 
Codes) 

Buffer size: 

745 bytes 

Rate input: 

Max. voltage: 230VAC (-20% / +15%) 
max. current: 2mA 

Pulse output: 

Wipe, according to DIN 42864 (S0 output) 
max. voltage: 265VAC/DC 
max. current: 50mA 
min. voltage: 5VDC 

Dimensions 

 

Reviews: