BA_373-E45_05_DEF_MJ_21
19
33 |
36
W. Baelz & Sohn GmbH & Co.
· Koepffstrasse 5 · 74076 Heilbronn · Germany ·
www.baelz.de Seite | Page
Motorized Linear Actuator
baelz 373-E45
Malfunction
Cause
Action required
Actuator not working
Power failure
Determine the cause and correct the
problem.
Defective fuse (in control cabinet)
Determine the cause and correct the
problem, replace the fuse.
Linear actuator incorrectly connected
Re-connect as specified on circuit
diagram (inside cover).
Short circuit caused by humidity
Determine the cause, dry the linear
actuator; if necessary, replace cover
seal and screws and/or fit protective
cover.
Short circuit caused by incorrect connection Connect correctly.
Motor winding damage caused, for example,
by high voltage or defective electronics
Determine cause, measure current
data, compare with nameplate and
specifications, dismantle linear
actuator and return for repair.
Voltage drop due to connecting cables being
too long and / or having insufficient cross-
section
Measure current data with linear
actuator, recalculate connecting
cables and replace as necessary.
Actuator running erratically,
constantly opening and
closing
Power fluctuations exceed permissible
tolerance
Improve power supply conditions.
Loose contact in supply line
Check and tighten connections
(terminal blocks).
Actuator stops intermittently
Valve jamming
Enable smooth valve movement.
Actuator does not move to
end position. Valve fails to
open / close
System pressure too high
Adjust system pressure.
Poor input signal
- interfering signals
- signal fluctuation
Check input signal at linear actuator,
correct the problem causing the
malfunction.
Linear actuator fails to move
or does not move correctly
to the position defined by
the input signal.
Circuit board defective
Replace circuit board, if necessary
dismantle actuator and return for
repair.
12.1 Checklist for operational malfunctions
Summary of Contents for BA 373-E45
Page 36: ......