INSTALLATION
WARNING
INSTALLATION INSTRUCTIONS GIVEN IN THE FOLLOWING ARE TO BE OBSERVED IN ORDER TO PROVIDE
FUNCTIONALITY AND SAFE OPERATION OF THE METER.
Installing the Sensor
Sensor
Gasket
1 Insert the gasket onto the threaded end of the sensor
2 Screw the sensor into the stainless steel mounting bracket or other mounting system that accommodates a
1 in NPT sensor or a 1-1/2 in G thread sensor
OTE:
N
Install the sensor at a maximum height (see table below) above the flume bottom (minimal measured level) with a
minimum distance above the maximum measured level
Sensor
Max
DL10
DL24
ULM 53
ULM 70
Minimum Height
2 in (50 mm)
4 in (100 mm)
8 in (200 mm)
6 in (150 mm)
Maximum Height
49 in (1250 mm)
9 8 ft (3 m)
19 7 ft (6 m)
6 6 ft (2 m)
3 Connect the sensor to the 4…20 mA input terminal on the bottom side of display board
Installation
Page 8
August 2021
HYB-UM-02509-EN-06