Meter Setup Menu
Application
Tank
A
Select for a tank application
Open Channel
A
Select for an open channel application
Sensor
Interval
S
Setup of time measurement interval(s); default value is 1 second; larger
interval (for instance, 300 seconds) is set when unit is powered from
battery
WarmUpTime
S
Powering time of sensor(s) before measurement; larger interval is set
when unit is powered from battery
LowerRangeValue
A
The minimum level value of used sensor = 4 mA in selected level units
For most level sensors, set to zero
UpperRangeValue
A
The maximum level value of used sensor = 20 mA in selected level units
For a DL10 sensor, set to 49 2 in (1250 mm)
For a DL24 sensor, set to 118 1 in (3000 mm)
For a ULM 53, set to 9 8 ft (3 m)
For a ULM 70, set to 6 6 ft (2 m)
Set the units in the Length parameter in the Measurement Menu
Offset
S
Level offset in selected level units, depends on sensor mounting position
If the sensor is mounted lower than the specified height, enter the
difference as a negative offset
Programming
Page 15
August 2021
HYB-UM-02509-EN-06