Transmitter Installation
Page 25
August 2019
DPP-UM-00256-EN-03
4…20 mA Output Module
The 4…20 mA Output Module interfaces with most recording and logging systems by transmitting an analog current signal
that is proportional to system flow rate Configure the 4…20 mA ISO-MOD via jumper selections for an internally powered
) or externally powered (
) module Do not exceed the maximum load for a particular supply voltage
See
200
100
300
400
500
600
700
800
900
1000
1100
12
14
16
18
20
22
24
26
28
Supply Voltage (VDC)
Lo
op L
oad (
O
hms)
Operate in the
Shaded Regions
Supply Voltage - 7 VDC
0.02
= Maximum Loop Resistance
Figure 21: Maximum 4…20 mA loads
Internal Power Configuration
Verify that jumpers are in place at JP1 and JP2 on the module See
In this configuration, the 4…20 mA output
is driven from a +24V DC source located within the DFX flow meter The 24V DC source is isolated from the DC ground
and earth ground connections within the DFX flow meter The module can accommodate loop loads up to 800 Ohms in
this configuration
OTEE:
N
The +24V internal supply, if configured to power the 4…20 mA output, shares a common ground with another
ISO-MOD (if installed) If another module is connected to earth ground, a ground loop may occur The solution to this
problem is to configure the 4…20 mA module for external power and use an external isolated supply to power the
4…20 mA loop
OUT (-)
IN (+)
I/O: 4-20 mA
P.N. D020-1045-100
ISO-MOD
JP2
JP1
INT PWR EXT PWR
Use Both
Jumpers
RTU/PLC
MONITOR
4-20 mA IN (+)
4-20 mA OUT (-)
Figure 22: Internally powered 4…20 mA