TOOLS AND MATERIAL

Required Tools

62658-000 Torx® Screw Driver (10 and 15 bits)

Suggested Tools

Electric drill

3/16" carbide tip masonry drills 

Common and Phillips Screwdrivers T-25 Wire Stapler and Staples

Touch reading device for installation verification

Required Material

63705-003 BadgerTouch Installation Kit for Remote

Applications, including:

(2) 55211-231 Screw, Phillips Head

(2) 62359-001 Screw Anchor 10-12 (1/4" drill bit required) 

(2) 34776-001 Cable Tie

Optional Material

56088 GE RTV-162 Adhesive Sealant

IDENTIFICATION

BadgerTouch Remote Modules are supplied as standalone 

modules for field connection to High Resolution Encoder 

(HRE) 

or 

Absolute Digital Encoder (ADE®) for all Recordall® Disc, Turbo, 

Compound, Combo, and Fire Series meters and assemblies. Each 

HRE or ADE is clearly identified on the face of the dial with an 

assembly number, unit of measure and meter model number The 

BadgerTouch Remote Module does not contain an identification 

number. The HRE or ADE register contains a unique identification 

number. The number is shown on the underside of the register 

cover. Interrogation of the HRE or ADE will display the ID number 

and the meter reading.

Figure 1: Identification – 

Touch Module

INSTALLATION

Unpacking

Carefully remove the BadgerTouch Remote Module (Figure 1) from 

the shipping carton. Locate the corresponding HRE or ADE for 

proper coordination during installation. Retain the contents of the 

installation kit for use in making connections to the HRE or ADE 

transmission line.

Location

To ensure proper operation of the BadgerTouch on-site meter 

reading system, the BadgerTouch Pit Module should be mounted 

through a predrilled hole in the pit lid. Minimum hole diameter 

required is 1-3/4". The Pit Module contains electronic circuitry that 

is totally encapsulated to enhance reliable performance in most 

locations, under most conditions.

Remote Module Installation

The remote module contains two screw terminals that require 

connection to the red and black lead wires of the HRE or ADE cable. 

The BadgerTouch system is not polarity sensitive.

Red Wire

Black Wire

Te rminals

Green Wire

Wire

Access

Po rts

Figure 2: Remote Module Connection

Locate the position of the two mounting holes on the outside of the 

building by using the remote module as a template. The Remote 

Module should be located in an easily accessible location but 

should be within 75 feet maximum wire distance to the water meter 

and the encoder using Belden 9770 wire. Additional wire length and 

other wire types may affect performance.

Drill a 3/16" wire entry hole at a suitable location in the building 

wall. Cut the protective gel cap off the end of the HRE or ADE cable. 

Feed the HRE or ADE cable from the water meter through the wall. 

Then cut the cable to proper length, making sure you have sufficient 

wire to make the connection to the Remote Module.

Wire access to the Remote Module may be from the rear, or through 

a bottom or top access port. When utilizing rear access, allow 

approximately 8" of extra cable behind the Remote Module to 

facilitate making the wiring connections. If using the bottom or top 

access port, the thin plastic area of the outer shroud needs to be 

snapped off to expose the wire access port. Use a small wire cutting 

pliers to snap the plastic.

BadgerTouch®

Automated Meter Reading System Remote Module

Models HREBT and ADEBT

BTA-UM-00232-EN-04 (June 2013)

Installation Data

Summary of Contents for BadgerTouch HREBT

Page 1: ...more information on connections To provide best results a maximum of 75 feet of wire Belden 9770 between the remote module and the encoder is allowed Other wire types may also affect performance If a...

Page 2: ...4545 West Brown Deer Rd PO Box 245036 Milwaukee WI 53224 9536 800 876 3837 414 355 0400 M xico Badger Meter de las Americas S A de C V Pedro Luis Ogaz n N 32 Esq Angelina N 24 Colonia Guadalupe Inn CP...

Page 3: ...is factory prewired to the HRE or ADE and does not require additional wiring in the field Construction The Badger Meter BadgerTouch pit module is constructed from high impact plastic material that is...

Page 4: ...rved The Americas Badger Meter 4545 West Brown Deer Rd PO Box 245036 Milwaukee WI 53224 9536 800 876 3837 414 355 0400 M xico Badger Meter de las Americas S A de C V Pedro Luis Ogaz n N 32 Esq Angelin...

Page 5: ...ch Pit Module should be mounted through a predrilled hole in the pit lid Minimum hole diameter required is 1 3 4 The Pit Module contains electronic circuitry that is totally encapsulated to enhance re...

Page 6: ...ote system can begin To perform the test a compatible reading device capable of reading Badger HRE ADE or Sensus protocol can be used The reading unit should be placed on the remote module and the met...

Page 7: ...holder and then tighten its locking nut so that the coil assembly is fully seated in the top of the holder Excess wire should be coiled up inside the pit and cable tied to avoid any damage Black Hous...

Page 8: ...36 800 876 3837 414 355 0400 M xico Badger Meter de las Americas S A de C V Pedro Luis Ogaz n N 32 Esq Angelina N 24 Colonia Guadalupe Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Middle East...

Page 9: ...es true water resistance due to the adhesive technology used to seal the glass dome to the corrosion resistant metal bottom Leak rates less than 10 6 cc sec as tested by a helium mass spectrometer are...

Page 10: ...1 High Side T1000 4 1 0 1 0 01 Low side M35 4 0 1 0 01 0 001 High Side T2000 6 10 1 0 1 Low Side M35 6 0 1 0 01 0 001 Resolution stated as individual high and low readings www badgermeter com ADE Badg...

Page 11: ...pond and that the proper HRE configuration has been supplied for the application THE HRE SHOULD ONLY BE CONNEC TED TO A BADGER METER APPROVED PRODUCT CONNECTION TO AN UNAPPROVED PRODUCT WILL VOID THE...

Page 12: ...rminal screw cavity and secure by tightening the Torx screw TESTING After connections are complete test the entire installation including the HRE wiring and remote or pit module for proper operation i...