Badger Meter 380CS Installation & Operation Manual Download Page 6

Page 6

 

      

 7-11

Series 380 Impeller Btu System

MECHANICAL INSTALLATION

General

The accuracy of flow measurement for all flow measuring devices is highly dependent on proper location of the sensor in the 

piping system. Irregular flow velocity profiles caused by valves, fittings, pipe bends, etc. can lead to inaccurate overall flow 

rate indications, even though local flow velocity measurement may be accurate. A sensor located in the pipe can be affected 

by air bubbles, floating debris, or sediment may not achieve full accuracy and could be damaged. Badger Meter flow sensors 

are designed to operate reliably under adverse conditions, but the following recommendations should be followed to ensure 

maximum system accuracy. 

 

 

1. 

Choose a location along the pipe where 10 pipe diameters upstream and 5 pipe diameters downstream of the 

sensor provide no flow disturbances. Pipe bends, valves, other fittings, pipe enlargements and reductions should not 

be present in this length of pipe.

2. 

The recommended location for the sensor around the circumference of a horizontal pipe is on top of the pipe. The 

sensor should never be located at the bottom of the pipe, as sediment may collect there. Locations away from the 

top-center on a pipe cause the impeller friction to increase, which may affect performance at low flow rates. Any 

circumferential location is correct for installation in vertical pipes. Rising flow is preferred to reduce effects of any 

trapped air.

Installing the Sensor Tee

1. 

Position the tee for unrestricted pipe flow for at least 10 pipe diameters upstream and 5 pipe diameters downstream 

of the tee.

2. 

Apply pipe compound over the first 3 or 4 threads of the mating pipe.

3. 

Thread the pipe into the sensor tee until hand tight.

4. 

Tighten the pipe an additional 1-1/2 turns, using a wrench.

ELECTRICAL INSTALLATION

1. 

The Series 380 requires an isolated 12-24 V AC/DC power supply.  To avoid ground fault conditions, the 380 power 

should not be shared with other devices. This is especially true when the RS-485 network connections are being 

utilized, where damage to the product or system could result.  

The power connections are labeled 1 and 2 and are not polarity sensitive. 

2. 

The RS-485 requires three connections: RS-485+, RS-485- and REF.  

The connections are labeled 1 (+), 2 (-) and 3 (GND). RS-485 is a high-speed connection and should be wired to meet 

TIA-EIA-485-A standards.   

This is especially true if a long cable run is involved or multiple devices are to be networked.

3. 

The pulse output is a simple solid state switch.  

The connections are labeled "PULSE OUTPUT 1" and "PULSE OUTPUT 2".  The switch is not polarity sensitive, however, 

be careful that the maximum voltage and current ratings are not exceeded. See "SPECIFICATIONS" on page 11 for 

details. 

Note: 

The pulse and RS-485 may be used simultaneously.

Summary of Contents for 380CS

Page 1: ...Series 380 Impeller Btu System 380CS HS Installation Operation Manual PN 880102 0001 Rev 4 7 11 IMPORTANT This manual contains important information READ AND KEEP FOR REFERENCE...

Page 2: ...Series 380 Impeller Btu System Page ii 7 11...

Page 3: ...ION 6 COMMISSIONING 7 RS 485 Network Configurations 8 RS 485 Network Configurations Modbus 8 RS 485 Network Configuration BACnet 9 SPECIFICATIONS 11 MECHANICAL 11 ELECTRICAL 11 Inputs 11 Output 11 MAT...

Page 4: ...Series 380 Impeller Btu System Page iv 7 11...

Page 5: ...nnection Setup includes energy measurement units measurement method communications protocol pulse output option fluid density and specific heat parameters Cold Service 380CS Designed for operating in...

Page 6: ...low flow rates Any circumferential location is correct for installation in vertical pipes Rising flow is preferred to reduce effects of any trapped air Installing the Sensor Tee 1 Position the tee for...

Page 7: ...f Zero parameter is the difference between T1 and T2 that will still read 0 energy rate If the Scaled Pulse Output is going to be used the user can select what the pulse is representing Energy or Flow...

Page 8: ...ode RTU or ASCII The Series 380 uses IEEE 754 Float Data Located in Read Holding Registers The Series 380 Data Format is Float 32 where the Data is stored across two Read Holding Registers In the case...

Page 9: ...Float Read Only Temp Coef 40017 40018 IEEE 754 Float Read Only Specific Heat 40019 40020 IEEE 754 Float Read Only Fluid Density 40021 40022 IEEE 754 Float Read Only RS 485 Network Configuration BACne...

Page 10: ...n Analog Value AV10 SerialNum dimensionless BACnet Protocol Implementation Conformance Statement BACnet Standardized Device Profile Device Profile Tested BACnet Smart Actuator B SA Supported BIBBs Sup...

Page 11: ...200 300 380HS 30 250 Ketron Brgs Aflas seals 220 280 380HS 30 250 Ketron Brgs Aflas seals 240 260 380HS 30 250 Ketron Brgs Aflas seals 250 230 380HS 30 250 Ketron Brgs Aflas seals Rating is based on...

Page 12: ...m Sensor Body Sizes Tee Sizes 0 75 1 1 25 1 5 and 2 NPT Recommended Design Flow Range 1 to 15 FPS Accuracy Flow Calculation 2 of flow rate within flow range 0 5 Repeatability RTD Meets IEC751 Class B...

Page 13: ...Page 13 7 11 Installation Operation Manual Intentional Blank Page...

Page 14: ...e to continuous research product improvements and enhancements Badger Meter reserves the right to change product or system specifications without notice except to the extent an outstanding contractual...

Reviews: