Badger Meter 340BN Installation & Operation Manual Download Page 8

8

12. To set the MS/TP address for the 340BN transmitter, open

the New Address pull-down menu and select the correct poll-
ing address which matches the polling address entered into
the master controller for this node of the BACnet network.
Press the Assign New Address button to transmit polling in-
formation to the 340BN transmitter.

13. To set the MS/TP baud rate for communication from the

BACnet

®

 buss to the Model 340BN transmitter, open the New

Baud Rate pull-down menu and select the desired value.  The
most common baud rate is 9600.  Press the Assign New Baud
Rate button to transmit the symbol rate to the Model 340BN
transmitter.  Press the Close button to return to the Main screen.

BACnet Diagnostic Utility

The MS/TP ReadBack diagnostic utility is provided as a helpful
tool to verify connection between the Model 340BN transmitter
and BACnet

 

network when installing a transmitter or while trouble-

shooting faulty communication between an individual node and
the master controller.  To use this utility, the Model 340BN trans-
mitter must be connected to a PC or laptop and the BACnet
network as outlined below.

1.

Connect the PC to the Model 340BN transmitter using
the Badger Meter Model A301 communications cable.
Plug the RS232 connector on the Model A301cable to
the 340BN socket labeled D.I.C. Comm Port, taking care
to properly align the tab on the plug and socket to main-
tain polarity.  Plug the DB9 connector on the opposite
end of the Model A301 cable to an available PC com-
munications port.  If a cable with a DB9 connector is
not available, a USB to DB9 adapter (e.g. IOGEAR
GUC232A) can be used.

2.

If not already installed, connect the Model 340BN trans-
mitter to the BACnet network.  Connect all three Model
340BN network terminals (+), (-), and REF to the
BACnet buss if the transmitter is the final node in a
given network.  Otherwise, connect only terminals (+)
and (-) to the BACnet buss.  Confirm the correct posi-
tion of jumpers on the Model 340BN transmitter.  For
the final transmitter in a given BACnet network, NT, PU,
and PD jumpers should be in “open” position.  Other-
wise, NT, PU, and PD should be in the “closed” posi-
tion.  Please refer to the Sample Wiring Diagram to
BACnet Network found on page 5.

3.

Open the Badger Meter Combo PC Software.

4.

Follow steps 5 through 7 found on page 6 to open the
Model 340BN Main screen.

5.

From the Main screen, select MS/TP ReadBack.

This will open the MS/TP Check screen as shown below.

Summary of Contents for 340BN

Page 1: ...BadgerMeter Inc Installation Operation Manual Model 340BN BACnet Energy Transmitter PN 941700 0012 3 07 ...

Page 2: ...try make precise measurements and produce accurate drift free outputs The Model 340BN is configured using Badger Meter Windows based programming software Calibration information for the flow sen sor units of measurement and type of temperature sensor may be preselected or entered in the field Btu transmitter information is available when connected to a PC or laptop computer This information includ...

Page 3: ...nap onto the mounting flanges allowing the Model 340BN to be attached to DIN 15 32 35 mm DIN rail systems Wall Mounting Optional metal and plastic enclosures are available for the Model 340BN The enclosure is first attached to the wall using fasteners through its mounting holes After wiring the transmitter may be attached to the enclosure with the terminal headers facing inwards using the slots in...

Page 4: ...low sensor red wire to Model 340BN Sensor Input Signal terminal and connect the flow sensor black wire to Model 340BN Sensor Input Signal terminal The bare wire con nects to the Sensor Input Shield terminal SDI Series standard pulse output option Connect SDI terminal number 3 to the Model 340BN transmitter Sensor Input Signal terminal and SDI terminal number 2 to the Model 340BN transmitter Sensor...

Page 5: ...mmon color lead is attached to terminal 3 The single color lead is attached to terminal 2 The RTD located closest to the flow sensor termed temperature sensor T1 should be connected to terminal block Temp 1 The RTD located far thest from the flow sensor termed temperature sensor T2 should be connected to terminal block Temp 2 Connecting the BACnet Buss As shown in the BACnet Sample Wiring Diagram ...

Page 6: ...Comm port taking care to prop erly align the tab on the plug and socket to maintain polarity Plug the Model DB9 connector on the opposite end of the Model A301 cable to an available PC communications port If a cable with a Model DB9 connector is not available a USB to DB9 adapter e g IOGEAR GUC232A can be used 3 Connect the Model 340BN transmitter to a power supply 4 Open the Badger Meter Combo PC...

Page 7: ...nds to actual changes in flow and energy A scale of 0 10 is used with 10 providing the greatest degree of smoothing Step 1 Select the flow sensor type and enter the K and Offset values See Note 1 Step 6 Select the desired units for energy rate and energy total Step 7 Press Send to transmit calibration data to the transmitter Step 8 Press Exit to close the Parameters Screen and return to the main s...

Page 8: ...lined below 1 Connect the PC to the Model 340BN transmitter using the Badger Meter Model A301 communications cable Plug the RS232 connector on the Model A301cable to the 340BN socket labeled D I C Comm Port taking care to properly align the tab on the plug and socket to main tain polarity Plug the DB9 connector on the opposite end of the Model A301 cable to an available PC com munications port If ...

Page 9: ...AV2 TotEnergy FALSE BTU kBTU MBTU kWh MWh kJ MJ AV3 Kfactor FALSE dimensionless AV4 Offset FALSE dimensionless AV5 TempMode FALSE dimensionless AV6 FFilterCoef FALSE dimensionless AV7 TFiltCoef FALSE dimensionless AV8 SpHtCapac FALSE BTU lb F AV9 Density FALSE lb gallon AV10 InTACoef FALSE dimensionless AV11 InTBCoef FALSE dimensionless AV12 InTCCoef FALSE dimensionless AV13 InTOffset FALSE C F AV...

Page 10: ...upported BIBBs Product Supported BIBBs BIBB Name Tested DS RP B ReadProperty B 340BN DS WP B WriteProperty B Standard Object Types Supported Product Object Type Creatable Deletable Tested 340BN Analog Input No No 340BN Analog Value No No 340BN Device No No Data Link Layer Options Product Data Link Options Tested 340BN MS TP Slave Baud rates 9600 19200 38400 76800 Segmentation Capability Product Se...

Page 11: ...odel A 301 programming kit containing 340BN software and Model A 301 programming cable is required for programming and setup SPECIFICATIONS Power Power supply options 12 24 VAC rms Tolerance 12 24 VDC Tolerance Current draw 70mA 12 VDC Flow Sensor Input Pulse type sensors Signal amplitude 2 5 VDC threshold Signal limits Vin 35V DC or AC peak Frequency 0 10kHz Pull up 15 VDC 2 kΩ Source Impedance S...

Page 12: ...on exists BadgerMeter Inc 6116 E 15th Street Tulsa Oklahoma 74112 918 836 8411 Fax 918 832 9962 www badgermeter com Please see our website at www dataindustrial com for specific contacts Copyright Badger Meter Inc 2007 All rights reserved Windows is a registered trademark of Microsoft Corporation BACnet is a registered trademark of American Society of Heating Refrigerating and Air Conditioning Eng...

Reviews: