Badger Meter 226SS Installation & Operation Manual Download Page 6

Series 200 Flow Sensors

1.  Set one set of hex/jam nuts so that the distance 

between the top surface of the hex nut and the top 
surface of the hex mounting adaptor is equal to the 
“D” dimension calculated above. Then adjust the other 
two sets of hex/jam nuts 1-1/2 inches below the first 
jam nut to allow clearance for the tool top yoke.

2.  Remove the tool split ring and clevis pin and slide 

tool bottom yoke into the groove on the sensor hex 
mounting adaptor and secure by replacing the clevis 
pin and split ring.

3.  Mark sleeve 2-3/4 inches from impeller end of metal 

sleeve. This mark is a stopping point to insure that 
impeller/bearing is not damaged. Open the bleed 
petcock valve on the hex adapter to relieve the 
pressure resulting from the sensor tube insertion. 
Carefully hand insert the Badger Meter hot tap 
flow sensor sleeve assembly into the hex mounting 
adapter until the mark lines up with the top of the 
hex mounting adapter. At this point the sleeve will 
have been inserted past the top two “O”-rings in the 
adapter (approx. 1 1-1/4 inches). Take care not to push 
the sensor past the mark on the sleeve as the impeller 
could be damaged if it strikes the closed valve.

4.  Fully extend tool by turning drive nut 

counterclockwise with a 15/16 inch socket or box 
wrench (not provided) until drive nut contacts tool 
and slide the positioning collar into the tool top yoke.

5.  Rotate tool so the threaded rod with the adjusted 

hex/jam nuts is centered in the top yoke of hot tap 
tool.

6.  Rotate sensor sleeve so positioning collar holes align 

with the threaded rods and flow direction label is in 
general direction making sure the positioning collar is 
located in the recessed area of the top yoke. Slide the 
top yoke of the tool over the positioning collar and 
secure by tightening the two thumbscrews on the top 
of the yoke.

7.  Close the bleed petcock and slowly open the isolation 

valve. Slowly turn the 15/16 inch drive nut clockwise 
to insert the sensor tube assembly through the 
valve and into the pipeline. Carefully guide the three 
threaded studs of the hex mounting adapter through 
the holes of the sensor positioning collar. Carefully 
lower the sensor until the positioning collar contacts 
the hex nut preset for the correct depth adjustment. 
Install the three lock nuts onto the threaded rods, 
tightening only the lock nut on the threaded rod with 
the preset hex/jam nut; then, bring the two remaining 
lock nuts down until they just contact the positioning 
collar. Do not tighten at this time

8.  Remove the Model HTT Insertion/Removal Tool, by 

loosening the two thumbscrews, removing the clevis 
pin and then sliding the insertion tool off the sensor. 
Then bring the two remaining sets of hex/jam nuts up 
to the underside of the positioning collar, and tighten.

9.  Align the sensor by first loosening the two set screws 

in the side of positioning collar with a 3/32 inch Allen 
wrench. Then align the sensor sight holes along the 
pipe axis using the alignment rod provided in the 
sensor installation kit. Ensure that the flow label arrow 
on the sensor matches the liquid flow direction inside 
the pipe. Tighten the positioning collar set screws. 
Note: As a backup to the flow label arrow, there is 
a small hole located beside the sight hole on the 
upstream side of the sensor.

ELECTRICAL INSTALLATION 
"STANDARD" SENSORS

1.  The metal collar on the top of the 220 sensors or an 

optional conduit cap on the Series 250 sensors will 
accept 1/2 inch threaded conduit fittings.

2.  Route the cable from the sensor to a Badger Meter 

flow monitor/transmitter.  The cable may be extended 
up to 2000 feet, using 2-conductor shielded 20 AWG 
or larger stranded copper wire. Be sure to leave 
enough flexibility in the cable or conduit to allow for 
future service of sensor, if necessary.

3.  When connecting to a Badger Meter flow monitor/

transmitter, locate the section of terminal strip on the 
monitor  labeled 

“SENSOR INPUT”

 or 

“SENSOR”

.  

Connect the red wire to 

“ IN”

, "

)

" or 

"

SIGNAL

" terminal and the black wire to 

“GND", 

"SIGNAL(-)”

, or "

COM

" terminal and the shield drain 

wire (if applicable) to 

“SLD”

.

4.  When interfacing with other equipment, consult 

manufacturer for input designations. The signal wave 
forms and power requirements are as shown in the 
specifications section. Refer to Technical Bulletin 
DTB-058 at www.badgermeter.com.

ELECTRICAL INSTALLATION "IR" 
SENSORS

The sensor leads are supplied with watertight caps over 
the ends. See Application Note DAB-031 and Technical 
Bulletin DID-003 at www.badgermeter.com.

1. DO 

NOT

 remove the plastic caps from the sensor 

leads until ready to splice.

2. Use 

twisted pair

 cable suitable for direct burial to 

connect the sensor to the transmitter, monitor, or 
controller. Multi-pair telecommunication cable or 
direct burial cables may be used.

3.  Make a water tight splice. Two part epoxy type 

waterproof kits are recommended. Be sure the epoxy 
seals the ends of the cable jacket.

4.  Make sure the epoxy is hardened before inverting the 

splice or dropping it in standing water.

Page 6

 

August 2012

Summary of Contents for 226SS

Page 1: ...Series 200 Insertion Style Flow Sensors Installation Operation Manual 872020 EN August 2012 Rev 8 IMPORTANT This manual contains important information READ AND KEEP FOR REFERENCE...

Page 2: ...and 226SS 4 If the Pipe is Depressurized and Drained 5 INSTALLATION INTO A PRESSURIZED PIPELINE USING MODEL HTT 5 ELECTRICAL INSTALLATION STANDARD SENSORS 6 ELECTRICAL INSTALLATION IR SENSORS 6 ELECTR...

Page 3: ...eter impeller flow monitor or transmitter Badger Meter non magnetic flow sensors provide an accurate rate of liquid flow as well as total accumulated flow A number of sensor models are offered which c...

Page 4: ...ure removal of sensor for service or cleaning if necessary HOT TAP INSTALLATION FOR 225BR 226BR AND 226SS Badger Meter Series 200 hot tap style liquid flow sensors are designed for use in cases where...

Page 5: ...flow sensor tube into the hex mounting adapter The sleeve should be inserted past the top two O rings in the adapter approx 1 to 1 1 4 inches Take care not to push the tube in too far as the impeller...

Page 6: ...wo remaining lock nuts down until they just contact the positioning collar Do not tighten at this time 8 Remove the Model HTT Insertion Removal Tool by loosening the two thumbscrews removing the clevi...

Page 7: ...or transmitter locate the section of terminal strip on the monitor labeled SENSOR INPUT or SENSOR Connect the red wire to IN SIGNAL or SIGNAL terminal and the black wire to GND SIGNAL or COM terminal...

Page 8: ...Series 200 Flow Sensors Page 8 August 2012...

Page 9: ...ndards Columns 4 and 5 The K value and Offset that should be used in our frequency equation Freq Gpm K Offset This equation describes the frequency of the output signal of all Badger Meter flow sensor...

Page 10: ...8 071 41 063 0 283 80 2 500 Std Wt Sch 40 8 625 7 981 40 086 0 281 80 2 500 Sch 60 8 625 7 813 38 288 0 279 80 2 500 Extra Strong Sch 80 8 625 7 625 36 315 0 276 80 2 500 PVC Class 125 8 625 8 095 41...

Page 11: ...11 400 12 000 22 inch Std Wt Sch 20 22 00 21 25 301 975 0 621 500 15 000 Extra Strong Sch 30 22 00 21 00 294 642 0 616 500 15 000 Sch 80 22 00 19 75 259 513 0 573 500 15 000 24 inch Std Wt Sch 20 24 0...

Page 12: ...tion the impeller in the cavity oriented as in step 4 so that the impeller blades point into the flow direction and toward the small alignment hole located beside one of the sighting holes on metal se...

Page 13: ...00 hex adapter valve bronze UNS C83600 Sensor Sleeve and Hex Adapter for 220SS and 226SS Series 300 stainless steel Temperature Ratings Standard version 2210F 1050C continuous service High temperature...

Page 14: ...Series 200 Flow Sensors This page intentionally left blank Page 14 August 2012...

Page 15: ...Installation Operation Manual This page intentionally left blank Page 15 August 2012...

Page 16: ...6 800 876 3837 414 355 0400 M xico Badger Meter de las Americas S A de C V Pedro Luis Ogaz n N 32 Esq Angelina N 24 Colonia Guadalupe Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Middle East a...

Reviews: