Badger Meter 226SS Installation & Operation Manual Download Page 10

Series 200 Flow Sensors

Column 1 

Column 2 

Column 3 

Column 4 

Column 5 

Column 6 

Suggested Operating 

Pipe Size 

Pipe O.D. 

Pipe I.D. 

    K

Offset 

Range (GPM) 

3 inch Sch 10S

3.500" 

3.260" 

5.009 

.090 

12-400 

Std. Wt., Sch 40 

3.5" 

3.068" 

4.362 

.063 

12-400 

Extra Strong, Sch 80 

3.5" 

2.900" 

3.858 

.043 

12-400 

PVC Class 125

3.5" 

3.284" 

5.094 

.093 

12-400 

PVC Class 160 

3.5" 

3.230" 

4.902 

.085 

12-400 

PVC Class 200 

3.5" 

3.166" 

4.682 

.076 

12-400 

4 inch Sch 10S

4.5" 

4.260" 

9.597 

.241 

20-600 

Std. Wt., Sch 40

4.5" 

4.026" 

8.34 

.229 

20-600 

Extra Strong, Sch 80 

4.5" 

3.826" 

7.354 

.188 

20-600 

PVC Class 125 

4.5" 

4.224" 

9.396 

.240 

20-600 

PVC Class 160 

4.5" 

4.154" 

9.013 

.240 

20-600 

PVC Class 200 

4.5" 

4.072" 

8.578 

.239 

20-600 

5 inch Sch 10S

5.563" 

5.295" 

16.305 

.250 

30-900 

Std. Wt., Sch 40 

5.50" 

5.047" 

14.674 

.248 

30-900 

Extra Strong, Sch 80 

5.50" 

4.813" 

13.165 

.246 

30-900 

6 inch Sch 10S

6.625" 

6.357" 

24.089 

.260 

50-1,500 

Std. Wt., Sch 40 

6.5" 

6.065" 

21.574 

.257 

50-1,500 

Extra Strong, Sch 80 

6.5" 

5.761" 

19.457 

.254 

50-1,500 

PVC Class 125 

6.625" 

6.217" 

22.853 

.258 

50-1,500 

PVC Class 160 

6.625" 

6.115" 

21.968 

.257 

50-1,500 

PVC Class 200 

6.625" 

5.993" 

21.068 

.256 

50-1,500 

8 inch Sch 10S

8.625" 

8.329" 

43.914 

0.286 

80-2,500 

Sch 20 

8.625" 

8.125" 

41.653 

0.283 

80-2,500 

Sch 30 

8.625" 

8.071" 

41.063 

0.283 

80-2,500 

Std. Wt., Sch 40 

8.625" 

7.981" 

40.086 

0.281 

80-2,500 

Sch 60 

8.625" 

7.813" 

38.288 

0.279 

80-2,500 

Extra Strong, Sch 80 

8.625" 

7.625" 

36.315 

0.276 

80-2,500 

PVC Class 125 

8.625" 

8.095" 

41.324 

0.283 

80-2,500 

PVC Class 160 

8.625" 

7.961" 

39.869 

0.281 

80-2,500 

PVC Class 200 

8.625" 

7.805" 

38.203 

0.279 

80-2,500 

10 inch Sch 10S

10.75" 

10.420" 

70.195 

0.321 

125-4,000 

Sch 20 

10.75" 

10.250" 

67.668 

0.318 

125-4,000 

Sch 30 

10.75" 

10.136" 

66.069 

0.316 

125-4,000 

Sch 40, Std.Wt. 

10.75" 

10.020" 

64.532 

0.314 

125-4,000 

Extra Strong, Sch 60 

10.75" 

9.750" 

61.016 

0.309 

125-4,000 

Sch 80 

10.75" 

9.564" 

58.644 

0.306 

125-4,000 

PVC Class 125 

10.75" 

10.088" 

65.431 

0.315 

125-4,000 

PVC Class 160 

10.75" 

9.924" 

63.272 

0.312 

125-4,000 

PVC Class 200 

10.75" 

9.728" 

60.733 

0.309 

125-4,000 

12 inch Sch 10S

12.75" 

12.390" 

104.636 

0.367 

175-5,000 

Sch 20 

12.75" 

12.250" 

102.553 

0.364 

175-5,000 

Sch 30 

12.75" 

12.090" 

99.347 

0.36 

175-5,000 

Std. Wt., Sch 40S 

12.75" 

12.000" 

97.576 

0.358 

175-5,000 

Sch 40 

12.75" 

11.938" 

96.369 

0.356 

175-5,000 

Sch 60 

12.75" 

11.625" 

90.441 

0.348 

175-5,000 

Extra Strong 

12.75" 

11.750" 

92.775 

0.351 

175-5,000 

Sch 80 

12.74" 

11.376" 

85.922 

0.342 

175-5,000 

PVC Class 125 

12.75" 

11.966" 

96.912 

0.357 

175-5,000 

PVC Class 160 

12.75" 

11.770" 

93.152 

0.352 

175-5,000 

PVC Class 200 

12.75" 

11.538" 

88.842 

0.346 

175-5,000 

 

Calibration Table for Pipe Sizes 3 Inches Through 36 Inches

Continued on Next Page

Page 10

 

August 2012

Summary of Contents for 226SS

Page 1: ...Series 200 Insertion Style Flow Sensors Installation Operation Manual 872020 EN August 2012 Rev 8 IMPORTANT This manual contains important information READ AND KEEP FOR REFERENCE...

Page 2: ...and 226SS 4 If the Pipe is Depressurized and Drained 5 INSTALLATION INTO A PRESSURIZED PIPELINE USING MODEL HTT 5 ELECTRICAL INSTALLATION STANDARD SENSORS 6 ELECTRICAL INSTALLATION IR SENSORS 6 ELECTR...

Page 3: ...eter impeller flow monitor or transmitter Badger Meter non magnetic flow sensors provide an accurate rate of liquid flow as well as total accumulated flow A number of sensor models are offered which c...

Page 4: ...ure removal of sensor for service or cleaning if necessary HOT TAP INSTALLATION FOR 225BR 226BR AND 226SS Badger Meter Series 200 hot tap style liquid flow sensors are designed for use in cases where...

Page 5: ...flow sensor tube into the hex mounting adapter The sleeve should be inserted past the top two O rings in the adapter approx 1 to 1 1 4 inches Take care not to push the tube in too far as the impeller...

Page 6: ...wo remaining lock nuts down until they just contact the positioning collar Do not tighten at this time 8 Remove the Model HTT Insertion Removal Tool by loosening the two thumbscrews removing the clevi...

Page 7: ...or transmitter locate the section of terminal strip on the monitor labeled SENSOR INPUT or SENSOR Connect the red wire to IN SIGNAL or SIGNAL terminal and the black wire to GND SIGNAL or COM terminal...

Page 8: ...Series 200 Flow Sensors Page 8 August 2012...

Page 9: ...ndards Columns 4 and 5 The K value and Offset that should be used in our frequency equation Freq Gpm K Offset This equation describes the frequency of the output signal of all Badger Meter flow sensor...

Page 10: ...8 071 41 063 0 283 80 2 500 Std Wt Sch 40 8 625 7 981 40 086 0 281 80 2 500 Sch 60 8 625 7 813 38 288 0 279 80 2 500 Extra Strong Sch 80 8 625 7 625 36 315 0 276 80 2 500 PVC Class 125 8 625 8 095 41...

Page 11: ...11 400 12 000 22 inch Std Wt Sch 20 22 00 21 25 301 975 0 621 500 15 000 Extra Strong Sch 30 22 00 21 00 294 642 0 616 500 15 000 Sch 80 22 00 19 75 259 513 0 573 500 15 000 24 inch Std Wt Sch 20 24 0...

Page 12: ...tion the impeller in the cavity oriented as in step 4 so that the impeller blades point into the flow direction and toward the small alignment hole located beside one of the sighting holes on metal se...

Page 13: ...00 hex adapter valve bronze UNS C83600 Sensor Sleeve and Hex Adapter for 220SS and 226SS Series 300 stainless steel Temperature Ratings Standard version 2210F 1050C continuous service High temperature...

Page 14: ...Series 200 Flow Sensors This page intentionally left blank Page 14 August 2012...

Page 15: ...Installation Operation Manual This page intentionally left blank Page 15 August 2012...

Page 16: ...6 800 876 3837 414 355 0400 M xico Badger Meter de las Americas S A de C V Pedro Luis Ogaz n N 32 Esq Angelina N 24 Colonia Guadalupe Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Middle East a...

Reviews: