Instruction 24-9448
3-20
Initial Setup
3.19 Language
Information on the display screen can be shown in English, French, or
Spanish. Select the desired language as follows:
1. Display the MAIN MENU by press-
ing the
MENU (F2)
button. If necessary,
press
ESC
until MENU appears above
F2
.
2. Use the
buttons to highlight SETUP, and
then press
ENT
to display the SETUP MENU.
3. Use the
buttons to highlight LANGUAGE
SELECTION, and then press
ENT
to display
The Language Selection Menu.
4. Use the
buttons to highlight the desired
language, then press ENT to activate the
selection and re-display the Setup Menu.
MAIN MENU
FUEL
PRESSURE
TEMPERATURE
MEMORY
SETUP
CALIBRATION
DIAGNOSTICS
STATUS
F1
F2
F3
MENU
SETUP MENU
(more)
Logging
Test ID
Username
Run/Hold Format
Language Selection
Button Sound
CAL Reminder Period
MENU
F1
F2
F3
Language Selection
English
Français
Español
06/28/06 11:45:30 AM
MENU
F1
F2
F3
Instruction 24-9448
5-2
Calibration
Any errors detected during warm-up will
be listed on the display immediately fol-
lowing warm-up. For example, the screen
to the right shows that the battery is low.
Correct any errors before proceeding. Refer
to Section 7.3 for a listing of error messages
and their meaning.
2. Display the MAIN MENU by pressing the
MENU (F2)
button. If necessary, press
ESC
until MENU appears above
F2
.
3. Use
the buttons to highlight
CALIBRATION, and then press
ENT
to dis-
play the CALIBRATION PASSWORD screen.
4. Before calibration can begin a 4-place alpha-
numeric password must be entered. Use the
and buttons to enter the password.
(Note that the default password is 1111)
5. Press the ENT key to accept the password.
If the correct password was entered the
CALIBRATION Menu will be displayed.
6. Use the
buttons to highlight the sensor to
be calibrated, and then perform the calibra-
tion procedure for that sensor as described in
the following sections.
5.3 Pressure Sensor
Calibration
This procedure calibrates the pressure sensor to a known pressure value.
Material Required:
Bellows
Manometer
Range: ±8 in. of water column (±20 mb)
Accuracy: ±0.01 in. of water column (±0.025 mb)
ERRORS DETECTED
Low Battery
MENU
F1
F2
F3
MAIN MENU
FUEL
PRESSURE
TEMPERATURE
MEMORY
SETUP
CALIBRATION
DIAGNOSTICS
STATUS
F1
F2
F3
MENU
Calibration Password
Enter Password
Menu
F1
F2
F3