4.3. Changing Alarm Level for 2-Channel, 1-Alarm Units
Step
Instructions
1
Connect voltmeter leads to pin 4 (-Ve) and
pin 1 (+Ve) on the CAL header.
2
Using the flat-blade screwdriver, adjust
potentiometer P3 until the reading on the DC
voltmeter corresponds to the desired input
alarm level.
P3
NOTE:
When adjusting the alarm level, a 0.4 to 2.0 VDC
reading on the voltmeter corresponds to a 4 to 20 mA value
for the input alarm threshold.
NOTE:
Both channels have the same alarm threshold.