MGS-350 Manual
14
6509-9000 Rev 1
Section 2. Installation and Wiring
WARNING:
Explosion hazard! Do not mount the MGS-350 in an
area that may contain flammable liquids, vapors, or aerosols.
Operation of any electrical equipment in such an environment
constitutes a safety hazard.
CAUTION:
The MGS-350 contains sensitive electronic
components that can be easily damaged. Do not touch nor
disturb any of these components.
NOTE:
The mounting location of the monitor should allow it to be
easily accessible for visual monitoring and servicing.
NOTE:
The monitor must be connected by a marked, suitably
located and easily reached switch or circuit-breaker as means of
disconnection.
NOTE:
Connect monitor power and signaling terminals using
wiring that complies with local electrical codes or regulations for
the intended application.
CAUTION:
An earth ground connection must be made when
using the vented metal enclosure or Exd enclosure. The safety of
this equipment is dependent on the integrity of the power supply
and the grounding of the MGS-350 enclosure.
IMPORTANT:
For main PCB connections, Bacharach suggests
using one of the following:
•
Belden 8761, 22 AWG single-pair shielded cable
•
Belden 8450, 22 AWG individually shielded pairs
•
an alarm type cable of 7/0.2 mm, 22 AWG.
NOTE:
All external connections are made to the motherboard
through a cable fitting. A cable tie should be fitted within
approximately 0.75” (20 mm) of the cable gland inside the
enclosure. The connectors are plug-and-socket type, and will
accept wire of 16-22 AWG. Cable runs should be kept to a
minimum.