![Bacharach HGM-MZ Maintenance And Troubleshooting Manual Download Page 15](http://html1.mh-extra.com/html/bacharach/hgm-mz/hgm-mz_maintenance-and-troubleshooting-manual_3292411015.webp)
Bacharach | THE MEASURABLE DIFFERENCE | New Kensington, PA, USA | Dublin, Ireland | Toronto, Canada | mybacharach.com
ZERO FILTER FAULT (0100) –
1. Indicates contamination in the purge air, could be caused by dirt, water or
refrigerant in the charcoal purge filter. The charcoal filter may need to be
changed.
2. Check to make sure the purge line has a filter on the end, “line end filter p/n
3015-3420”
3. Check to see where the purge air is coming from, the purge air must be from a
clean dry source.
GAIN SET FAULT (0200) –
1. Indicates sensor gain (digipot) is outside acceptable range. (see HGMMZ voltage
adjustment bulletin)
2.
If the gain set fault keeps showing up it could be an indicator of a failing IR
sensor.
LOOP FAULT
(0010) –
1. This would only be displayed if the dual 4-20 ma dc option card was installed and
one or both current loops are open. (unconnected to load or without shorting
jumpers)
2. Check the wiring to load/monitoring circuit on both 4-20 mA loops to make sure of the
connections or install shorting jumpers.
CONFIG FAULT
(0080) –
1.
There is an error in
HGM Setup Screen in the
Number Zones Installed field. The
number of zones installed is equal to the number of hoses connections on the side;
Note the number of Zones being used.
BUMP GAS TESTING
BUMP TESTS:
Gas test (or “bump test”) each zone using the bump gas method
described below to ensure that the monitor is operating properly, the alarms operate, and
that each zone’s gas path is clear.
a. This procedure uses “bump gas” (dilurothane) as an inexpensive test gas.
Virtually any brand of keyboard cleaner or “canned air” (readily available at most
computer and variety stores) contains this refrigerant and is sufficient to perform a
bump test.