background image

 

5.  The first port on the left includes two pieces of 18-2 that should be connected to each         

     slave 

module in both evaporators at  #1 and #2 terminals.  These connections will shut down  

     the system if there is 

ever a high water condition in either evaporator. They are connected  

    

     parallel to each safety float. Also 

in the first port there is a piece of 18-6 that is color coded per  

     our standard operating instructions to be affixed 

to the VH620 Keyboard Display, the temp   

 

     sensor, and the humidity sensor (see Page 6 in  “Power 

To the  Evaporator”).  Second port  

 

     from the left is power, 14-2 with ground, 115V. Lastly the third and 

fourth outlets hold each 14-6  

     jumper cable, that is also color-coded.  These run to each evaporator slave 

module inside of   

     each stainless steel enclosure. 

 

6.  Make sure that the unit is covered tightly with each cover.

Slave Control Module

 

7.  From left to right.  The first two terminals should be connector to the 18-2 leads from  

 

     

 

     port one in the master control module.  Terminals 3, 4/5 (one white lead), 7,8.9 and 10 will be   

     

connected to each color coded lead from the 14-6 cable that you run from the Master Control   

     Module.  

Replace the cover firmly.

Evaporator Set Up, continued

 

8. Wrap the TXV and refrigeration solenoid with ESP Heat block (#HB34) or comparable    

     

    product. 

Braze the refrigerant solenoid to the liquid line. Remove the txv bulb and braze in the  

    suction line to the line exiting the 

condenser. Re-attach the bulb when cool.

3

Summary of Contents for BCS2000

Page 1: ...yboard and master to slave control jumper 6 Condensing unit pad Condensing Unit Set Up 1 Place a suggested model on a firm level location pad for outdoor applications or add 4 anti vibration pads to each corner of the condensing unit for indoor use Place in an area with adequate air flow 2 Braze in suction and liquid lines to condensing unit 3 Bring 3 8 copper tubing from the liquid line of the co...

Page 2: ... the back wall for adequate air distribution 2 Run the 1 4 drain line from the pump in the evaporator through the ceiling cap and out to a suitable location Heat tape any portion susceptible to freezing 3 Attach template to the ceiling Remove the stainless steel outer enclosure from the base of the unit Attempt to locate any mounting holes below ceiling joists for secure attachment with 8 wood scr...

Page 3: ...th outlets hold each 14 6 jumper cable that is also color coded These run to each evaporator slave module inside of each stainless steel enclosure 6 Make sure that the unit is covered tightly with each cover Slave Control Module 7 From left to right The first two terminals should be connector to the 18 2 leads from port one in the master control module Terminals 3 4 5 one white lead 7 8 9 and 10 w...

Page 4: ...of the green condensate pump in each evaporator 11 For indoor applications run 1 4 vinyl condensate drain tube from the evaporator to a suitable location 12 Do not replace cover until unit test is complete Controller Display Set Up 1 Install double gang box and cut out the blank plate to accept the Bacchus Temp Humidity Keyboard VH620 The keyboard can be mounted inside or outside of the room Run 1...

Page 5: ...d and are not intertwined or crossed XH10P Humidity Sensor 8 The microprocessor has been preprogrammed for 55F and 50 RH To change either setting E Depress the up and down v keys together for more than three seconds to unlock the keyboard F Push the Temp or Humidity Set Key and immediately Release 18NB1 G Use the up and down v keys to change the value H Push the appropriate set key again and wait ...

Page 6: ... pressure drop Take the difference between actual temperature and your reading from a PT chart to calculate 4 System Start up Before replacing stainless steel enclosure cover power up the system to make sure water solenoid is opening correctly The misting nozzle will be open Remove power and replace the cover Power up the evaporator and let the system pull down At temp set point the refrigerant so...

Page 7: ...e could be bad Compressor fans controller or Pump Alarm Signaling Message Cause Outputs P1 Thermostat probe failure compressor and heating outputs off on dehumidification system only P3 Humidity probe failure humidity regulation off HA High temp alarm outputs unchanged LA Low temperature alarm outputs unchanged HHA High humidity alarm outputs unchanged HLA Low humidity alarm outputs unchanged In t...

Page 8: ...tage 208 230 1v Electrical compressor rla 10A 11A 8A 12 1A compressor lra 53A 51A 43A 49A cond Unit MFS 20A 30A 15A 17 6A cond Unit mca 13 4A 13 4A 11 3A 12 1A BTU capacity 40F 4857 6250 10200 100 amb 12 185 suc 110 amb Phone 937 665 0424 Fax 937 890 6664 8 ...

Reviews: