Section Assembly of Optional Three-Piece Cells
Table 2.
Minimum Vertical Dimension and Spreader Bar Length for Optional Three-Piece Lift for Single Air Intake FXV and CXVB Units
Model Number
Lower Section
Plenum Section
Coil Section
FXV
CXVB
H
W1
W2
H
W3
H
W4
FXV-0806x-x-x
CXVB-x-0806-x
3'-6"
8'-6"
4'-0"
3'-1"
4'-11"
3'-1"
3'-5"
FXV-0809x-x-x
CXVB-x-0809-x
4'-4"
8'-6"
4'-0"
3'-1"
4'-11"
3'-1"
3'-5"
FXV-0812x-x-x
CXVB-x-0812-x
4'-4"
8'-6"
4'-0"
5'-3"
4'-11"
5'-3"
3'-5"
FXV-0818x-x-x
CXVB-x-0818-x
5'-3"
8'-6"
4'-0"
8'-2"
4'-11"
8'-2"
3'-5"
FXV-1212x-x-x
CXVB-x-1212-x
4'-4"
11'-10"
5'-3"
5-'3"
6'-1"
5-'3"
5'-2"
FXV-1218x-x-x
CXVB-x-1218-x
5'-3"
11'-10"
5'-3"
8'-2"
6'-1"
8'-2"
5'-2"
W1
H
W2
W1
H
W2
Figure 6a.
Coil Section Lift
Figure 6b.
Plenum Section Lift
NOTE:
For the lower section, see
Figure 1a
on
page 4
.
WARNING:
Failure to use lifting
provisions can result in a dropped
load causing severe injury, death,
and/or property damage. Lifts
must be performed by qualified
riggers following BAC published
Rigging Instructions, and generally
accepted lifting practices. The
use of a supplemental safety
sling may also be required if the
lift circumstances warrant its
use, as determined by the rigging
contractor.