WWW.BALTIMOREAIRCOIL.COM
4
Rigging
Refer to
Tables 1, 2, and 3 and Figures 1, 6, and 7 for each section’s required minimum
spreader bar length W1 and W2 (if applicable) and the recommended minimum vertical
dimension “H”. Refer to
Figures 1, 6, and 7 for dimension reference.
Failure to use lifting provisions can result in a dropped load causing severe injury, death,
and/or property damage. Lifts must be performed by qualified riggers following BAC
published Rigging Instructions, and generally accepted lifting practices. The use of a
supplemental safety sling may also be required if the lift circumstances warrant its use, as
determined by the rigging contractor.
NOTE:
For weight information, refer
to the submittal drawing package.
Table 1.
Minimum Vertical Dimension and Spreader Bar Length for Single Air Intake FXV and CXVB Units
Model Number
Lower Section
Upper Section
FXV
CXVB
H
W1
W2
H
W1
W2
FXV-0806x-x-x
CXVB-x-0806-x
3'-6"
8'-6"
4'-0"
3'-1"
8'-6"
3'-2"
FXV-0809x-x-x
CXVB-x-0809-x
4'-4"
8'-6"
4'-0"
3'-1"
8'-6"
3'-2"
FXV-0812x-x-x
CXVB-x-0812-x
4'-4"
8'-6"
4'-0"
5'-3"
8'-6"
3'-2"
FXV-0818x-x-x
CXVB-x-0818-x
5'-3"
8'-6"
4'-0"
8'-2"
8'-6"
3'-2"
FXV-1212x-x-x
CXVB-x-1212-x
4'-4"
11'-10"
5'-3"
5'-3"
11'-10"
4'-2"
FXV-1218x-x-x
CXVB-x-1218-x
5'-3"
11'-10"
5'-3"
8'-2"
11'-10"
4'-2"
NOTE:
All single-cell and multi-cell
units must be rigged one section
at a time.
CROSSFLOW COIL PRODUCTS
Unit Rigging & Assembly
2
Figure 1a.
Lower Section Lift
Section Assembly of Two-Piece Cells
Figure 1b.
Upper Section Lift
WARNING:
Failure to use lifting
provisions can result in a dropped
load causing severe injury, death,
and/or property damage. Lifts
must be performed by qualified
riggers following BAC published
Rigging Instructions, and generally
accepted lifting practices. The
use of a supplemental safety
sling may also be required if the
lift circumstances warrant its
use, as determined by the rigging
contractor.