Section 5 - Restarting Your Battery
We strongly recommend keeping the battery charged to avoid activating the internal low battery
voltage disconnect.
If your DC system shuts down, the battery may require re-starting. Please use the following procedure:
1.
Turn off ALL DC and AC loads
2.
Connect charging source/s and switch ON
3.
Hold the “Reset” button on top of the battery for 5-10 seconds
4.
Release and wait 7 seconds
5.
Power should now be restored and charging will commence
6.
When the SOC (State of Charge) is above 20%, loads can be switched on if required
By continuously tripping the low voltage disconnect of the battery you may cause damage to sensitive
electronic equipment that is attached to the battery. I.E. battery chargers, solar controllers, inverters,
stereo equipment etc - all of which are not covered under the battery warranty.
Page 8
Enerdrive B-TEC G2 Manual (Rev. 2.1)
EPL-100BT-12V-G2, EPL-125-12V-G2
EPL-200BT-12V-G2
FLAT BATTERY
RESET BUTTON
FLAT BATTERY
RESET BUTTON