The data label is located on the top left-hand side of the front panel or on the inside of the door. Please ensure that the
gas supply matches the data label
Ventilation
Ventilation must be in accordance with AS5601 - Gas Installations. In general, the appliance should have adequate
ventilation for complete combustion of gas, proper flueing and to maintain temperature of immediate surroundings
within safe limits. It is
strongly
recommended that this appliance is installed under an extraction hood.
The appliance shall be installed with an exhaust system comprising a hood and duct system. The hood shall be made
of a material which is impervious to fat, grease and vapour. It shall be constructed so it can be readily and efficiently
cleaned. Its inside faces shall be smooth and free of obstructions and all joints shall be grease tight.
The hood shall be located so as to effectively ventilate the steamer and shall extend at least 150 mm beyond the
perimeter of the steamer. The exhaust duct system shall be adequately sized and shall not get connected to any other
ventilating or exhaust system.
As suitable grease trap shall be provided to prevent grease vapour entering the exhaust system and shall be located to
avoid constituting a fire hazard and be readily accessible for regular cleaning.
Unless adequately protected a hood and a duct shall be fitted at least 450 mm from any combustible material and so
that the lower edge of the grease filter is no less than 1.1 meters above the cooking surface.
Combustible Surfaces
Clearances to combustible surfaces must be in accordance with AS/NZS 5601.1 -
Gas Installations
,
clause 5.12.4.5.
Install on a flat, solid, fire proof base.
Leave at least 200mm between the appliance and the side and rear walls.
The Steamer shall be installed so that a clear space of 200mm is maintained between the sides of the steamer and any
other appliance.
No combustible material shall be located within 200mm of the steamer.
Gas Connection
The gas connection is male 3/4” BSP and is situated at the
front of the appliance below the main body frame.
It is
situated 210mm from the left-hand side of the appliance, 670mm from the rear of the appliance and approximately
145mm from the floor. The appliance can be connected with rigid pipe as specified in AS5601.
For fixed installation
models we recommend connection with 20mm copper tube and an Australian certified isolating valve.
BEFORE CONNECTING NEW PIPE TO THIS APPLIANCE, THE PIPE MUST BE BLOWN OUT THOROUGHLY TO REMOVE
ALL FOREIGN MATERIAL. FOREIGN MATERIAL IN THE BURNER AND GAS CONTROLS WILL CAUSE IMPROPER AND
DANGEROUS OPERATION.
Water and Drainage Connection
The water inlet and water drains can be routed through the base of the unit. Water isolation valves are fitted to all water
inlets. Ensure water is flushed through before final connection.
Water waste outlet is located on the left-hand side of the waste gutter of the appliance. The water inlets and water
drains should be connected with rigid copper pipes.
We strongly advise against the usage of plastic/PVC piping
for connection of waste outlet.
We advise that the unit must be connected along with a water filtration system to ensure optimum performance
of the unit and failure to do so may void the B&S warranty.