Examples of installation 

)LJ$YRLGDFFXPXODWLRQRIDLU

)LJ0RXQWDYDOYHRUDUHJXODWRUDIWHUWKHIORZPHWHU

Note:

  During  installation  it  must  be  ensured  that  no 

water can enter the electronic unit during operation. 

3.1 

Installation for cooling metering 

Note: 

It  is  recommended  that  the  flow  meter  installed 

on the hot side. 

When  installing  as  a  cold  meter  it  is  essential  that  the  black 
cover  on  the  measuring  tube  is  pointed  to  the  side  or 
downwards  in  order  to  avoid  problems  with  condensation 
forming.  
Fit  the  electronic  unit  separate  to  the  volume  measurement 
tube,  e.g.  on  the  wall.  Make  a  loop  downwards  in  order  to 
prevent  condensation  running  along  the  connected  lines  into 
the electronic unit.  

7UDQVGXFHUFRYHU

)LJ5HFRPPHQGHGLQVWDOODWLRQSRVLWLRQIRUFRROLQJPHWHULQJ

3.2 

Installation of qp 150 

Note: 

Use flange bolts with a length of at least 100 mm 

to install the flanged body in the pipeline. 

As an assembly aid two M10 threads are monted on the flange. 
The  threads  allow  the  use  of  stainless  steel  eye  bolts,  for 
example, for a lifting device.  
The  measurement  insert  in  the  flanged  body  should  be 
positioned  on  the  top.  This  allows  a  simple  exchange  of  the 
measurement insert (see chapter 5).  

3.3 

Electronic unit 

The ambient temperature of the electronic unit must not exceed 
55 °C.  Avoid  direct  sunlight.  For  water  temperatures  between 
10 °C  and  90 °C  you  can  fit  the  electronic  unit  on  the  volume 
measurement unit or on the wall.  

Aligning electronic unit 

Proceed as follows to align the electronic unit: 

1.

Pull the electronic unit off the volume measurement unit.

2.

Turn the electronic unit to the left or right through 90° or
180° as required.

3.

Push the electronic unit onto the adapter plate in this
position until it engages.

)LJ(OHFWURQLFXQLWLQVWDOODWLRQSRVLWLRQ

Wall fitting (split fitting) 

Fit  the  electronic  unit  to  the  wall  at  water  temperatures  below 
10 °C and above 90 °C.  
For wall mounting proceed as follows: 

Pull the electronic unit off the adapter plate.

Unscrew the adapter plate from the volume measurement
unit.

Fit the adapter plate to the wall.

Push the electronic unit onto the adapter plate.

)LJ$GDSWHUSODWHDQGZDOOILWWLQJ

3.4 

Power supply 

The  flow  meter  is  equipped  with  a  long  life  battery  for  5  or  9 
years  of  operation.  You  can  take  the  operating  time  from  the 
dial plate. 

Warning:

 Do not open the batteries. Do not bring battery 

into contact with water or expose to temperatures above 
80 °C.  Dispose  of  used  batteries  at  suitable  collection 
points. 

Note:

 Only batteries approved by the manufacturer may 

be installed. 

3.5 

Interfaces 

The  flow  meter  is  equipped  with  an  optical  interface  in 
accordance with EN 62056-21 as standard.  
In addition, the flow meter is equipped with a pulse output and 
is delivered with a 2m two wire cable. The connecting cable can 
be  lengthened  with  a  cable  2 x 0.75mm

2

.  A  distributing  box  is 

recommended. 