Operating instructions
Use and maintenance manual
13
VERIFY WITH THE TESTER THAT THE CURRENT
ISN’T LOWER THAN 220V (control when the door’s
working) if the current is lower than 220V control the
input
13
VERIFY WITH THE PROGRAMMER THAT THE BUS
VOLTAGE ISN’T LOWER THAN 300V (SYSTEM
CONDITION – BUS VOLTAGE) (control when the
door’s working) if the voltage is lower than 300V
control the input.
13
VERIFY WITH THE PRORAMMER THE MOTOR
UPTAKE (SYSTEM CONDITION- MOTOR CURRENT
with motor 0,75kw can’t be higher than 7A;with motor
1,5 kw can’t be higher than 9A, control when the
door’s working) if the door exceeds the threshold
lower the opening HZ
14
THE PHOTOCELL DOESN’T
WORK
14
CONTROL THAT IN THE VICINITY THERE AREN’T
ANY OTHER PHOTOCELLS THAT COULD CAUSE
REFLECTION (try to darken the photocells)
(the door closes but the photocell
doesn’t reverse the curtain)
14
CONTROL THAT WITH THE PHOTOCELL CABLES
THERE AREN’T ANY HIGH VOLTAGE CABLES
(motor ,motor brake, flashing lights, power line) (take
to the control board separated cables in different
pipes, separate the low voltage 12-24V from the high
voltage
≥
100V)
14
PUT THE MINUS OF THE RECEIVER (black cable,
blue wire) ground
15
WITH
OPEN
DOOR
(locked)
THE
CURTAIN
SLOW
DOWN
15
SET
THE
MOTOR
BRAKE
(remove
the
fan
cover
and
close
of
a
quarter
turn
of
the
dial
brake
adjustement,
then
make
tests
to
reach
the
optimum)