Installation and Operating Instruction
2. Installation
3. Detection area
6. Settings carried out using remote control (optional)
Remote control LUXOMAT
®
IR-PD
1. Check Battery:
open battery compartment by pressing the
plastic springs together and removing the
battery-holder.
2. IMPORTANT
Please pay attention, that the setting is Potentio-
meter 1 at “TEST” and Potentiometer 2
not
at
“SUN”. All values which have been program-
med using the remote control will be deleted in
the event of power failure in the position “TEST/
SUN”. Please switch Potentiometer 2 over to
“MOON” or any other value.
Caution:
Settings with remote control supersede the
settings by courtesy of potentiometers.
LUXOMAT
®
PD5-M-1C-Clip
1. Mounting preparations
Work on the 230 V mains supply
may only be carried out by qualified
professionals or by instructed persons
under the direction and supervision of
qualified skilled electrical personnel
in accordance with electrotechnical
regulations.
Disconnect supply before installing!
When in Master/Slave mode of
operation, the Master-appliance must
always be installed at the location
where there is least daylight.
The product enters an initial 60-second
self-test cycle, when the supply is first
connected. The occupancy detector is
ready for operation.
4. Self test cycle
The
LUXOMAT
®
PD5-M-1C-Clip is supplied
with a 90 cm long, 5 x 0.75, colour-coded
cable and is pre-wired.
The detector has been specially developed
for clipping onto fluorescent lamps of size
T5+T8.
It is particularly suitable for use with
suspended light-strips or for ceiling appli-
cations where holes caused by installation
are to be avoided. Two clip sizes of the
type required are enclosed. Carry out the
clipping-on procedure as follows:
The height-adjustable clip can be inserted
in the housing easily as long as the mark-
ings on the clip-shaft and the housing are
in line with each other. Once the correct
distance to the light has been established,
lock the shaft by rotating through 90° in
an anti-clockwise direction.
Option:
Wall bracket for remote
control IR-PD
IR-PD
IR-PD-Mini
5. Putting into operation / Settings
Follow-up time for light control
The time can be set infinitely variably at between
15 sec. and 16 min.
Symbol
TEST
: test mode (every movement switches on
the light for a period of 1 second, switching it off for a
period of 2 seconds after that regardless of the level of
brightness)
Twilight-switch for light control (relay 1)
The switch-on value for the light can be set at between 10
and 2000 Lux. Using the rotary control, the luminance set
points can be set as desired.
Symbol
:
Night-time operation
Symbol
: Daytime/Night-time operation
Mounting
height
Range (circular detection) T=18°C
seated
walking
across
walking
towards
2.00 m
r = 2.00 m
r = 4.00 m
r = 2.00 m
2.50 m
r = 2.50 m
r = 5.00 m
r = 3.00m
3.00 m
r = 3.00 m
r = 6.00 m
r = 3.70 m
3.50 m
–
r = 7.00 m
r = 4.30 m
4.00 m
–
r = 8.00 m
r = 4.80 m
4.50 m
–
r = 9.00 m
r = 4.50 m
5.00 m
–
r = 10.00 m r = 6.00 m
GB
Reset when open:
Deletes all values
set with the
remote control;
the settings on
the potentiometer
apply
Unlocking device
or
or
Lock device
Permanent tamper protection
Fully automatic/semi automatic
mode (see page 2, point 5)
max
50
Lux
1500
Lux
ON
OFF
��
���
����
���
��
���
��
���
max
50
Lux
1500
Lux
ON
OFF
t < 5 s
Settings for relay
Channel 1:
Settings for master with remote control
Note:
The buttons for channel 2 (
R2
) have
no function for the PD5-M-1C-Clip.
��
���
��
���
Target value for brightness
Automatic reading in of the current light value
as a new target light value
Lag times for channel 1
Pulse function for channel 1,
1s every 9 s on motion detection
The pulse function can only be selected in fully automatic mode.
Activate test mode when closed
To deactivate:
press reset
Resetting when closed
The lighting relay is switched off, i.e.
opened and the follow-up times reset.
Permanent protection against sabotage
This function blocks the unit permanently (green LED is
illuminated). This operating mode can only be activated
during the period of 5 seconds after pressing the “lock“
button. This status will only permit actuating the function
“Light on/Light off”. The procedure for leaving this mode is as
follows:
1. Switch off the current
2.
Apply current for 31 - 59 seconds (green LED flashes)
3.
Switch of the current again
4.
Apply current, wait for selftest cycle
5.
Open detector
Light on/off when closed
The light will remain switched on/off for as long as move-
ments are detected in the areas of coverage. Once the last
movement has been detected, the light will remain on for the
duration of the follow-up time as per setting.
The appliance will then return independently to the mode
selected (Fully or Semi-automatic).
��
���
����
���
Explanation of button functions
max
50
Lux
1500
Lux
ON
OFF
t < 5 s
120 60 50
40
30
15
10
A
16 10
5
2
1
30
15
TEST
2000
1200
600
200
40
5