10 m
20 m
Sensorandpowersupplyinonecase
Power supply:
230 V~+6 %/-10 %
Power consumption:
<1 W
Ambient temperature:
-25°C–+40°C
Degree of protection/class:
SMIP20,withaccessoryIP54,
FCandFMIP20withaccessoryIP23/II
Settings:
locallyandbyremotecontrol
Light values - IR-PDim:
50-1500Lux
Parallel operation:
Master/Slave
Area of coverage:
narrowdetectionarea,idealforcorridors
Range of coverage Ø H 2.5 m / T=18°C:
seated7 m/tangential40 m/radial20 m
Recommended height for mounting:
2-3 m
Light measurement:
dartificiallight
Lux values - Potentiometer:
10-2000Lux
• 1 Relay/Channel for light-connection
Type of contact
:NOC/withpretraveltungstencontact
Contact load:
2300 W,230 V~,10 Acos (
ϕ)
=1/
1150 VAcos (
ϕ)
= 0.5
Time-settings:
1-30min./Test
Max. no. of series-connected electronic ballasts:
dependingontypeandmake,totalconnectable140 µF.
Dimensions H x Ø [mm]
SM
FC
FM
PD4-M-DIM-C
76 x 101 103 x 97 84 x 97
Visible portion when built into ceiling:
30 x 97 mm
Technical data PD4-Slave-DIM-K
Electricaldatasameasabove,butjustonechannelfor
signalingmotiondetection
Declaration of Conformity:
Theproductcomplieswith
thelowvoltagerecommendation2006/95/ECandthe
EMVrecommendation2004/108/EC.
12. Technical data PD4-M-DIM-C
MAN
5
591
–
0
2_12/200
8
13. LED-functional indicators, fault-finding
ThefunctionalindicatorsinthecaseoftheLUXOMAT
®
PD4-M-DIM-C(redandgreenLED‘s)
Red LED indicating self-checking mode (over a period
of 60 seconds following mains‘-supply lock-on)
Flashing at intervals of 1 second
EEPROM/memoryempty
Flashing rapidly
EEPROM/memorycontainsinformation
Red LED as an indicator of status
Flashing irregularly
Movementsaredetectedwithintheareaofcoverage
Flashing regularly
Detectoridentifiesbright,lightoff
(dependentuponoperatingmode)
Not illuminated
Detectoridentifiesdark,lighton
(dependentuponoperatingmode)
Flashing extremely rapidly
Toobright/Toodark/Undefined
Red LED as an acknowledgement of receipt for
commands from the remote control
Illuminated for 2 seconds
Signalvalidlyreceived
Illuminated for 0.5 seconds
Not-acceptedcommand,detectorblocked
Flashing extremely rapidly
Not-acceptedcommand,occurs,forexample,when
anattemptismadetoinputtwilight-valuearetoo
brightortoodark
Green LED as an acknowledgement of receipt for
commands from the remote control
Lights up for 3 seconds
Semiautomaticorusersignalcorrectlyreceived
Green LED as an indicator of status (only for status
“Permanent protection against sabotage”
)
Flashing irregularly
Movementaredetectedwithintheareaofcoverage
Flashing regularly
Detectoridentifiesbright,lightoff
(dependentuponoperatingmode)
Not illuminated
Detectoridentifiesdark,lighton
(dependentuponoperatingmode)
lluminated for 2 seconds
Signalvalidlyreceived
(dependentuponoperatingmode)
Mounting height
2.5 m
40 m
20 m
16 m20 m
1
2
1
quer zum Melder gehen
frontal zum Melder gehen
Unterkriechschutz
walking across
walking towards
2
6. Manual Dimming - Preset / User
(for IR-PDim functions see page 1)
Youcandimmanuallybypressingthepushbutton
foralongtime(>2sec.).Whenthebuttonisreleased,
thecurrentdimmingvalueisretained.Uponrenewed
dimming,thedimmingdirectionisreversed.
PRESET
–
theluminancesetpointissetduringstart-up
operationbytheinstallerandremainsunchanged.
The luminance set-point configured through manual
dimmingisonlyappliedforthetimebeing.
Caution:
Theconstantlightregulationisnowdeactivated!
The currently set artificial light is retained independent
oftheambient/daylightbrightness!
Afterswitchingoffandthenbackon,theoriginallyset
luminanceset-pointisreset=constantlightregulation
isactivated.
USER
- can only be activated via the remote control!
Theluminanceset-pointischangeduponeachmanual
dimmingandre-adjustedbytheuser(Conformation
throughrelayclicking!)
Theconstantlightregulationremainsactivated!
5. Fully / Semi automatic mode
(for IR-PDim functions see page 1)
Fully automatic operation
Inthisoperatingmode,thelightingswitchesautomati-
callyonandoffforincreasedcomfort,dependingon
presenceandbrightness.
Semiautomatic operation
(Semiautomatic can only be activated via the remote
control!)
Inthisoperatingcondition,inordertogainincreased
savings,thelightingisenergizedonlyafterbeingmanu-
allyswitchedon.Switch-offtakesplaceautomatically.
Thesemiautomaticmodebasicallybehaveslikethefully
automaticone.However,thedifferenceisthatswitching-
onmustalwaysbecarriedoutmanually!
Asmany(closer-contact)buttonsasdesiredcanbewired
inparallelonthe“S”buttoninput(ON/OFFDimm).
7. Manual Switching
Youcanswitchthelightingonandoffmanuallyby
pressingthepushbuttonforashorttime.Itwillstayonor
off as long as people are detected plus the configured
followuptime.
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
8. Range of Coverage
9. Wiring diagrams
11. Article / Part-Nr. / Accessory
Push button operation
For manual switching push
the button only a short time (0.2 - 0.5 sec.)! To dim
push the button until the wished light level is arrived.
Master-/ slave-operation. The master is the only one to
read the light level and to switch the connected loads.
Independant of the light level the slave units react to mo-
vements only by sending impulsions via the dry contact.
No load can be connected to the dry
contact. The master-dim-occupancy detec-
tors can not be switched into parallel. For
that application please prefer the master- /
slave-installation. It is recommended to put
the master the furthest possible postion
away from the natural light source.
1-10
VDC
Terminal connection for push button operation
MASTER
Terminal connection for master-/ slave-operation
MASTER
SLAVE
R R N N L L
-
+ S L N L' R
10. PD4-M-DIM-C - Connections
Connections PD4-M-DIM-C-FC/-FM
Connections Plug-in socket
PD4-M-DIM-C-SM
–
+ N
R
–
+
L
S
SLAVE
L'
1-10 V
N
Type
SM
FC
FM
PD4-M-DIM-C (Master)
92218
92217
–
PD4-S-DIM-C (Slave)
92442
92444
92445
LUXOMAT
®
Remote control:
IR-PDim(incl.wallbracket)
92200
Accessory:
BSKBallbasketguard
92199
Wallbracketforremotecontrolasreplacement 92100
CoveringIP23
92206
WallbracketSM
92441
+
–
N
L' L
S
R
+
–
SLAVE
1-10 V
1-10 VDC
-
+ S L N L' R