Sensor and power supply in one case for onwall-, ceiling- 

and flushmounting

Power supply:

 230 V~ +6 %/-10 %

Power consumption:

 < 1 W

Ambient temperature:

 -25°C – +40°C

Degree of protection/class:

  SM IP54, FC and FM IP20 / II

Settings:  

locally and by remote control

Light values:

 10 - 2000 Lux

Parallel operation:

 Master/Slave

Area of coverage:

 circular 360°

Range of coverage Ø H 2.5 m / T=18°C:

 

 

seated 6.4 m / tangential 24 m / radial 8 m

Recommended height for mounting:

 2 - 3 m

Light measurement:

 Mixed light, da artificial light 

Lux values:

 5 - 2000 Lux

• Relay/Channel 1 for light-connection

Type of contact

: NOC/with pretravel tungsten contact

Contact load:

 2300 W, 230 V~, 10 A cos (

ϕ)

=1 /  

1150 VA cos (

ϕ)

= 0.5 

Max. no. of series-connected electronic ballasts:

depending on type and make, total connectable 140 µF. 

DIM-Outputs:

   PD4-DIM 

1 x (1-10 V) 

 

PD4-DUO-DIM   2 x (1-10 V)

Max. no. of series-connected electronic ballasts: 

 

max. 50 electronic ballasts by one single supply with  

max. 100 m cable run and a conductur cross-section of  

0.75 mm²

Time-settings:

 1 - 30 min. / test

Dimensions HxØ [mm]

 

SM 

FC 

FM

PD4-M-DIM 

76 x 101  103 x 97  74 x 97

PD4-M-DUO-DIM 

95 x 106  103 x 106  74 x 106

Visible portion when built into ceiling:

 30 x 97 mm

Technical data PD4-Slave

Electrical data same as above, but just one channel for 

signaling motion detection.

 

Declaration of Conformity: 

The product complies with 

the low voltage recommendation 2006/95/EC and the 

EMV recommendation 2004/108/EC.

13. Technical data PD4-M-DIM/-DUO-DIM

10. Wiring diagrams

11. PD4-DIM/-DUO-DIM - Connections

Type

SM

FC

FM

PD4-DIM (Master)

92147

92247

92248

PD4-DUO-DIM (Master)

92271

92272

92273

PD4-S (Slave)

92142

92254

92163

LUXOMAT

®

 Remote control:

IR-PDim (incl. wall bracket) 

92200

Accessory:

BSK Ball basket guard   

92199

Wall bracket for remote control as replacement  92100

Occupancy detectors - Covering IP23 

92206

12. Article / Part-Nr. / Accessory

MAN 5

55

– 0

2_12/200

8

In case the sensing area of the LUXOMAT

®

 PD4-DIM/

DUO-DIM is too large or areas are being covered that 

should not be monitored, the range can be reduced or 

limited through use of the enclosed masking clips (e).

9. Exclude sources of interference

8. Range of Coverage

6.  Manual Dimming - Preset / User 

(for IR-PDim functions see page 1)

 

You can dim manually by pressing the pushbutton 

for a long time (> 2 sec). When the button is released, 

the current dimming value is retained. Upon renewed 

dimming, the dimming direction is reversed.

PRESET

 

 the luminance set point is set during start-up 

operation by the installer and remains unchanged. 

The luminance set- point configured through manual 

dimming is only applied for the time being. 

Caution: 

The constant light regulation is now deactivated!

The currently set artificial light is retained independent 

of the ambient/daylight brightness!

After switching off and then back on, the originally set 

luminance set-point is reset = constant light regulation 

is activated.

USER

 

- can only be activated via the remote control!

The luminance set-point is changed upon each manual 

dimming and re-adjusted by the user (Conformation 

through relay clicking!)

The constant light regulation remains activated!

5.Fully / Semiautomaticmode

(for IR-PDim functions see page 1)

Fully automatic operation

In this operating mode, the lighting switches automati-

cally on and off for increased comfort, depending on 

presence and brightness.

Semiautomatic operation

(Semiautomatic can only be activated via the remote 

control!)

In this operating condition, in order to gain increased 

savings, the lighting is energized only after being manu-

ally switched on. Switch-off takes place automatically.

The semiautomatic mode basically behaves like the fully 

automatic one. However, the difference is that switching-

on must always be carried out manually!

As many (closer-contact) buttons as desired can be wired 

in parallel on the “S” button input (ON/OFF Dimm).

7. Manual Switching 

 

You can switch the lighting on and off manually 

by pressing the pushbutton for a short time. It will 

stay on or off as long as people are detected plus the 

configured follow up time.

14. LED-functional indicators, fault-finding

The functional indicators in the case of the LUXOMAT

®

 

PD4-DIM/DUO-DIM-MASTER (red and green LED‘s)

Red LED indicating self-checking mode (over a period 

of 60 seconds following mains‘-supply lock-on)

 

Flashing at intervals of 1 second

  

EEPROM/memory empty

Flashing rapidly

 

EEPROM/memory contains information

Red LED as an indicator of status

 

Flashing irregularly

 

Movements are detected within the area of coverage

Flashing regularly

 

 Detector identifies bright, light off  

(dependent upon operating mode)

Not illuminated

 

 Detector identifies dark, light on  

(dependent upon operating mode)

Flashing extremely rapidly

 

Too bright / Too dark / Undefined

Red LED as an acknowledgement of receipt for  

commands from the remote control 

Illuminated for 2 seconds

 

Signal validly received

Illuminated for 0.5 seconds

 

 Not-accepted command, detector blocked

Flashing extremely rapidly

 

 

 Not-accepted command, occurs, for example, when 

an attempt is made to input twilight-value are too 

bright or too dark

Green LED as an acknowledgement of receipt for  

commands from the remote control

 

Lights up for 3 seconds

 

Semi automatic or user signal correctly received

Green LED as an indicator of status (only for status 

“Permanent protection against sabotage”

Flashing irregularly

 

 Movement are detected within the area of coverage

Flashing regularly

 

 Detector identifies bright, light off  

(dependent upon operating mode)

Not illuminated

 

 Detector identifies dark, light on  

(dependent upon operating mode)

lluminated for 2 seconds 

Signal validly received  

(dependent upon operating mode)

PD4-DIM

PD4-DUO-DIM

Push button operation

 For manual switching push 

the button only a short time (0.2 - 0.5 sec.)! To dim 

push the button until the wished light level is arrived.

Separate reading of the lux levels for both 

channels, but only one switching channel!

 

For manual switching push the button only a short 

time (0.2 - 0.5 sec.)! To dim push the button until the 

desired light level is arrived.

  

  

             

1-10 VDC

Terminal connection for master-/ slave-operation

MASTER

SLAVE

  

             

R  R  N  N  L  L

L'  N  L  S  +  -

 

     

 

              

Terminal connection PD4-M-DUO-DIM

Channel 1 

1-10 VDC

Channel 2 

1-10 VDC

SLAVE

 

R  S  L  L'  N

+ +

Master-/ slave-operation. The master is the only one 

to read the light level and to switch the connected 

loads. Independant of the light level the slave units 

react to movements only by sending impulsions via 

the dry contact.

 

No load can be connected to the dry 

contact. The master-dim-occupancy detec-

tors can not be switched into parallel. For 

that application please prefer the master- / 

slave-installation. It is recommended to put 

the master the furthest possible postion 

away from the natural light source.

  

             

1-10

VDC

Terminal connection for push button operation

MASTER

  

+

             

R  L'  N  L  S

24 m

8 m

6.4 m

24 m

360°

Mounting height

2.5 m

1

2

walking across
walking towards
seated

e

Connection PD4-DUO-DIM-FM/-FC/-SM

Connection example PD4-DIM-FM

max

50

Lux

1500

Lux

ON

OFF

max

50

Lux

1500

Lux

ON

OFF

+

+

N

L' L

S

R

+2

+1

 –

1-10 V

SLAVE

1-10 V

+

N

L' L

S

R

+

 –

SLAVE

1-10 V

max

50

Lux

1500

Lux

ON

OFF

2

1

12 m

12 m

8 m

6.4 m

24 m

360°

Mounting height

2.5 m

2

1

quer zum Melder gehen 
frontal zum Melder gehen
sitzende Tätigkeit