24.  Reset the detector

If the double lock is activated, the detector can be opened again as 

follows:
• 

Disconnect operating voltage

• 

Connect operating voltage for 31sec. to 59 sec.  

• 

Disconnect operating voltage again

• 

Connect operating voltage again and wait for the self testing

• 

Open detector

With this procedure, the remote control programmed values are not 

deleted (before activation of the double lock).

If the setting is not changed by remote control after deactivation of 

the double lock, the detector changes in the double locked mode 

again after a period of 30 minutes. This way the detector cannot be 

unlocked during an accidental power failure.
Alternatively, the detector can be reset in this way: 

Set potentiometer A to “Sun” and potentiometer B to “Test”. The de-

tector now is in test mode and the potentiometer settings are active. 

All operating LEDs are flashing for three seconds.
Except of the INI ON/OFF setting, the detector is reset to factory 

setting or the setting of the potentionmeter.
Pushing the “RESET” button on the remote control, in opened mode, 

will delete all of the values which were set by the remote control 

(beside of INI ON/OFF) and set the detector back to  

its factory settings.

Factory settings

 

The detector is delivered with the following factory  

settings: lux value: 500 Lux, follow-up time: 10 minutes. 

Starting the detector in the factory program the initialisation 

mode starts with a constant flashing of the three operating  

LEDs.

23.  Manual Dimming - Preset / User  

 

(long press when closed)

You can dim manually by pressing the external push button or the 

remote control buttons "min/max" – for a long time  

(> 2 sec.). When the button is released, the current dimming 

value is retained. Upon renewed dimming, the dimming direction 

is reversed.

max

50

Lux

1500

Lux

ON

OFF

     Two different operating modes are selected  

in the opened state.

Changing the mode is done by pressing the "double lock" button. 

Each time the button is pressed, the current operating mode is 

indicated:

Red shines for 3 sec.  = Preset

Green shines for 3 sec.  = User

PRESET – 

the set value brightness is set during start-up operation by 

the installer and remains unchanged. The set value brightness config-

ured through manual dimming is only applied for the time being. 
The constant light regulation is now deactivated! The current set 

artificial light is retained independent of the ambient/daylight 

brightness! After switching off and then back on, the original set 

set value brightness is reset = constant light regulation is activated.

USER can only be activated via the remote control

The set value brightness is changed upon each manual dimming 

and re-adjusted by the user. The constant light regulation remains 

activated!

22. 

Manual Switching

(short press when closed) 

  

max

50

Lux

1500

Lux

ON

OFF

You can switch the lighting on and off manually by pressing the 

pushbutton or the remote control button “Light ON/OFF” for a 

short time. It will stay on or off as long as people are detected 

plus the configured follow up time.

17. Light regulation

The detector has two different integrated light control algorithms. 

The set value for the first algorithm is adjusted by potentiometer 

(LUX) on the device. Very small light amounts, which shine 

directly to the detector, have as result that the set value brightness 

is exceeded.
The second algorithm has an integrated daylight compensation. 

Therefore, it is necessary that the detector analyses the switched 

light quantity. This algorithm can only be used by remote control. 

The programming of the set value and the measurement of the 

light quantity is carried out in two steps: 

In the open state

•  The set value is adjusted without daylight (please darken the 

room) by using the remote control.

•  Measuring the light quantity will be initiated by a long press 

(> 3 sec.) of the test button. The detector turns the light on 

for 5 min. at 100 %. Then the light will turn on and off for a 

short time and stays on after that. This measuring process 

is shown by a flashing green LED (10 sec. off/ 1sec. on). 

This measuring process is required for each change of the 

set value.  
If the setting “permant orientation light” is chosen, the func-

tion only will be active after the measuring process is done.

If the measuring process is not performed, the detector performs 

it automatically when the ambient light is less than 50 lux for 1h.

M

A

N

 8

67

7_

PD

2-

M

-D

A

LI/

DS

I-1

C

_F

C

_23

061

5_

1

18.   Full / Semi-automatic mode

   

max

50

Lux

1500

Lux

ON

OFF

 

The mode is changed using the button "Light" in the open state.

Each time the button is pressed, the current operating mode is 

indicated by the LEDs

:

Red shines for 3 sec.  = Full automatic mode 

Green shines for 3 sec.  = Semi-automatic mode 

Full automatic operation

 

In this operating mode, the lighting switches automatically on 

and off for increased comfort, depending on presence and 

brightness.

Semi-automatic operation 

In this operating mode, the light turns on only after a manual 

switching, for an increased savings success (see section 22). 

Switching off is automatically or manually (see section 22). 

The semi-automatic mode basically behaves like the full automatic 

mode. The only difference is that the switching on has to be done 

by hand. 

In case motion is detected within the 10 sec. after elapse of the 

follow-up time, the detector switches the light on again and the 

follow-up time starts again. If there is no motion detected within 

the 10 s after elapse of the follow-up time, the light has to be 

turned on manually.

INI-OFF/ON mode:   

Turn off or turn on the light during the self-test cycle of 

6

0 sec. The last state is active. Factory setting is that the 

light is on during initialisation.
When INI OFF is chosen, the detector does not switch 

on the light after voltage supply. Even upon detected 

movement the light is switched on only after 60 sec.

Startup behavior

:    

The set value can be reached in two ways after 

switching on. The detector switches the lights on at 10 % 

and then adjusts upwards (min button) or it switches the 

light on at 100 % and regulates down (max button). 

This is confirmed by a short flashing of the red and 

white LED as well as the lighting. Factory setting is that 

the detector switches the light on at 100 %.

Reset of electronic ballasts

 

If required the connected EB can be reset and preset 

parameter can be deleted. Press the button “Reset” 

for 3 seconds in initialisation mode.

!

19.  Settings during the Self-test cycle

In the first 60 seconds after connecting the AC voltage, the 

following functions can be set:

20. Test mode/Reset

Test mode 

Use “Test” button for activating the test mode. 

Use the “Reset” button to deactivate it.

Reset in closed state 

The lighting is switched off, and the follow-up times are 

reset.

Reset in open state

Pressing the button for >3 sec. deletes all settings 

(except of INI ON/OFF) and the detector is reset to 

factory state.

!

21. 100 h function 

(long press (> 3 sec.) when closed) 

max

50

Lux

1500

Lux

ON

OFF

Before the lamp can be dimmed, the dimming function has 

to be suppressed for a certain time in order to burn in the 

lamps.

T5 fluorescent lamps: 80 h

T8 fluorescent lamps: 100 h
For activating the function, press button “Light ON/OFF” in closed 

state. During this time, the detector only switches the light ON or 

OFF. A dimming to the set value does not take place. After having 

activated the function, the red and green LED flash alternately. 

By pressing the button “Light ON/OFF” again, it is possible to 

deactivate the function before the time has elapsed.
Failure to comply to the burn-in would lead to reducing the life of 

the lamp. A further disadvantage could be unwanted random vari-

ations in light intensity.

!