B.E.G. LUXOMAT PD2-M-DALI/DSI-1C Installation And Operating Instruction Download Page 1

Installation and Operating Instruction for 

B.E.G.

 - Occupancy detector PD2-M-DALI/DSI-1C-FC

LUXOMAT

®

PD2-M-DALI/DSI-1C

EN

 1. Product information

• 

 Occupancy detector for daylight-dependent lighting 

control

• 

  DALI/DSI interface for controlling digitally dimmable 

electronic ballasts as a group 

• 

 One additional switching channel for controlling lights 

and HVAC (heating, ventilation, air conditioning) devices

• 

 Switching between DSI and DALI program by remote  

 

control or DIP switch

• 

 Extension of the detection area by Slave devices is 

possible

• 

 Set value brightness, follow-up time – LIGHT/HVAC and 

orientation light adjustable

• 

Manual switching and dimming via pushbutton possible

• 

Orientation light function

2. Operation

The presence detector controls the light automatically according 

to people present (movements) and the ambient brightness.
The integrated light sensor constantly measures the ambient light  

and compares it with the set value brightness on the detector. If 

the ambient light is sufficient, lighting will not be switched.  

If the ambient light level is below the set value brightness, a 

movement activates the lighting in the room.

The detector switches the light off despite of a person being pre-

sent if there is enough natural light for 5 min or if no movement 

is detected for one follow-up time. 

 3. Safety information

Work on the 110-240 V mains supply may only be 

carried out by qualified professionals or by instructed 

persons under the direction and supervision of quali-

fied skilled electrical personnel in accordance with 

electrotechnical regulations.

Disconnect supply before installing!

This device is not suitable for disconnection.

Mounting the cover ring, after introduction of the 

power cable (FC version).

4. Mounting 

68 mm

A circular opening of diameter 68 mm must be produced in the

ceiling. Having connected up the cables in accordance with

regulations, the detector is inserted into the opening as shown in

the drawing and fixed into position with the assistance of the 

spring clips.

5.   Position DIP switches, LEDs and 

Potentiometers

PD2 

False ceiling

mounting

C

B

A

Light 

measurement

DALI_D

SI

HV

AC_

LI

GHT

 

VA_HA

1

2

3

6. Self test cycle/Startup behavior

The product enters an initial 60-second self-test cycle, when the 

supply is first connected. During this time the device does not 

respond to movement and stays on.

7. Putting into operation / Settings

Brightness value for constant light control 

(Potentiometer A)

The brightness set value can be defined between 

10 and 2000 lux. The potentiometer enables a free 

selection of the brightness value.
Symbol

 

:    Night-time operation  

Symbol

 

:   Day-time operation 

(Light evaluation inactive)

Follow-up time for light control (Potentiometer B)

The follow-up time can be set to 1 to 30 minutes.
Symbol 

TEST

: test mode  

Irrespective of the brightness, every movement switches 

the light on for 1s, then off again for 2s.

Follow-up time for orientation light (Potentiometer C)

The follow-up time can be set infinitely variably at 

between 5 and 60 minutes. Manually switching ON/

OFF the orientation light.

“ON” for permanent orientation light

“OFF” for deactiviation of orientation light

Follow-up time for device control (Potentiometer D)

The follow-up time can be adjusted between 5 min. and

120 min. The delay is active from a set time of >15 mi-

nutes. This delay is about 5 min. If no other movements 

are detected during this time, the delay starts again.

Impulse function 

The impulse function can be used to control external 

HVAC systems. All 9 sec. will be set an impulse of 

2.5 sec.

Alarm impulse

In order to initiate an alarm impulse, there have to be 

three detected movements within a period of 9 sec.

This function can be used to display a presence in the 

room on external visualizations. All 9 sec. will be set an 

impulse of 2.5 sec.

The device does not fulfil the requirements of DIN 

EN50131-2-2 and therefore cannot be used in 

professional intrusion detection systems.

DIP switch functions

DIP 1

Full automatic mode

Semi-automatic mode

DIP 2

HVAC function

Light control*

DIP 3

Operation mode DALI

Operation mode DSI

 

* If you select “LIGHT”, the switching relay R2 operates synchro-

nously to the DALI light channel. The potentiometer R2 has no 

function in this setting.

Potentiometer  A

 Brightness (constant light control) channel 1

Potentiometer  B

 Follow-up time (light) channel 1

Potentiometer  C

 Follow-up time (orientation light)

Potentiometer D

 Follow-up time (device control) channel 2

LED I

   green

LED II  

red 

LED  III  

white

8. Wiring diagram

Standard mode with Master/Slave

L

N

L

N

N

N

S

Master

Slave

R

L

L

R

-

+

L‘

T1

DA1

M1

T2

DA

DA

E1     DALI/DSI

9. Manual switching and dimming

By pressing the push button, the phase can be given to the S

terminal.
To turn on or off the light, press the push button briefly. The light 

will remain on or off, as long as people are detected plus the 

follow-up time.
With a long press of the push button the light will be dimmed 

manually. When releasing the button, the current brightness value 

is retained.

With renewed long press of the push button, the dimming direction 

is reversed. 
Taking the phase to the R terminal by using a button, the HVAC

channel can be switched with a short key press.

10. Range

!

 

 

 

Connected Slave devices must have the same phase 

as the Master device.

R1

TE

1

3

6

22

18 16

10

30

25

LUX

40

2000

600

1200

200

R2

A

120

60

5

15

30

40

50

20%

60

5

10

50 30

O

FF

ON

R1

TE

1

3

6

22

18 16

10

30

25

LUX

40

2000

600

1200

200

R2

A

120

60

5

15

30

40

50

20%

60

5

10

50 30

O

FF

ON

R1

TE

1

3

6

22

18 16

10

30

25

LUX

40

2000

600

1200

200

R2

A

120

60

5

15

30

40

50

20%

60

5

10

50 30

O

FF

ON

!

R1

TE

1

3

6

22

18 16

10

30

25

LUX

40

2000

600

1200

200

R2

A

120

60

5

15

30

40

50

20%

60

5

10

50 30

O

FF

ON

A

!

!

!

!

The light sensor should be mounted on the opposite

side of the window.

In Master/Slave operation the Master device must

always be installed at the site with less daylight.

!

!

D

I

II III

LEDs

10 m

6 m

4 m

10 m

360°

2.50 m

2

1

1

2

quer zum Melder gehen 
frontal zum Melder gehen
Unterkriechschutz

Walking across
Walking towards
Seated