10 

 

White 

Brown 

Green 

Yellow 

Gray 

Pink 

Blue 

Red 

WSD2M31010 

10-30 

VDC 

AIN1 

AIN2 

AIN3 

DIN1 

GND 

GND 

GND 

* Wiring Chart Abbreviations: 

10-30VDC = 10-30V DC Power Input 

AIN1 = Analog Input #1 

AIN2 = Analog Input #2 

AIN3 = Analog Input #3 

DIN1 = Digital Input #1 

GND = Ground Input

 

 

TERMINAL BLOCK CONNECTIONS – THERMOCOUPLE & THERMISTOR 

Thread the thermocouple and thermistor wires through the conduit and attach them to the terminal block. 
 

 

 

MOUNTING THE NODE 

Wzzard industrial nodes may be mounted either with screws or temporarily with built-in magnets. The 

included anti-skid disk may be attached to bottom of unit to prevent slipping on metal surfaces. 

Flange Mounting

 - Wzzard nodes may be mounted via their mounting ears. (M5, #10) 

 

 

Summary of Contents for Wzzard WSD2C31010

Page 1: ...Wzzard Mesh Wireless Sensors Intelligent Edge Nodes Wireless Sensing Platform USER MANUAL...

Page 2: ...wa IL 61350 USA Phone 815 433 5100 Fax 815 433 5105 Advantech B B SmartWorx European Headquarters Westlink Commercial Park Oranmore Co Galway Ireland Phone 353 91 792444 Fax 353 91 792445 www advantec...

Page 3: ...Restoring Node to Factory Default 11 Battery Replacement 11 Connecting Your Sensor to Wzzard Commercial Node Model 13 MOunting Options Commercial Node 13 Adhesive Strip Mounting 13 Mounting Bracket P...

Page 4: ...ENERAL SPECIFICATIONS ALL MODELS INDUSTRIAL COMMERCIAL 36 RADIO SPECIFICATIONS ALL MODELS INDUSTRIAL COMMERCIAL 37 MECHANICAL DRAWINGS 38 Wzzard Industrial Node Models 38 Wzzard Commercial Node Models...

Page 5: ...id End user agrees to accept all liability for loss of or damages to the returned product during shipment Advantech B B SmartWorx shall repair or replace the returned product at its option and return...

Page 6: ...network management and comprehensive security features The platform uses full SmartMesh IP networking and time synchronized channel hopping to provide up to 99 999 connectivity even in the most demand...

Page 7: ...t connection model only 2 AA 3 6V Thionyl Chloride Lithium batteries External antenna Quick Start Guide Anti Skid disk WZZARD COMMERCIAL NODE MODEL PACKAGE INCLUDES Wzzard Mesh Wireless Sensor Node fo...

Page 8: ...Note UL C1 D2 rating is voided when using non UL specified batteries Remove the four 4 black screws that hold the top of the Wzzard node in place Connect your sensor CONDUIT NODE MODELS Thread the in...

Page 9: ...VDC AIN1 AIN2 DO1 DIN1 GND GND GND Wiring Chart Abbreviations 10 30VDC 10 30V DC Power Input AIN1 Analog Input 1 AIN2 Analog Input 2 AIN3 Analog Input 3 DIN1 Digital Input 1 D01 Digital Output 1 GND...

Page 10: ...al Input 1 GND Ground Input TERMINAL BLOCK CONNECTIONS THERMOCOUPLE THERMISTOR Thread the thermocouple and thermistor wires through the conduit and attach them to the terminal block MOUNTING THE NODE...

Page 11: ...iguration button for 5 seconds until the Status LED turns off The node will retain all settings including the associated network if the node has been claimed It will not reset the device back to facto...

Page 12: ...ip is to insert a small flathead screwdriver between the batteries and the clip parallel to the batteries and give the screwdriver a gentle twist This will remove the clip without damage Note As with...

Page 13: ...Pin 6 Do Not Use DIN1 Thermistor Input AIN1 AIN2 Common GND Pin Abbreviations DIN1 Digital Input AIN1 Analog Input AIN2 Analog Input GND Ground THERMISTOR BREAKOUT CABLE PIN OUT PIN AIN1 AIN2 Door Swi...

Page 14: ...t into deep sleep Press the Status Sleep Reset configuration button for 5 seconds until the Status LED turns off The node will retain all settings including the associated network if the node has been...

Page 15: ...to log in and claim your gateway The configuration of the Wzzard Mesh sensor network is done at 3 levels 1 Gateway Network Level When the gateway is selected in the tree you can turn node discovery on...

Page 16: ...een Centigrade and Fahrenheit etc CREATE AND LOCK THE NETWORK 1 Wake Up The Node Press and hold Status Sleep Reset configuration button for 5 seconds until the Status LED comes on and starts blinking...

Page 17: ...ick the checkbox next to each node Click the Claim Nodes button to prevent the nodes from joining another open network All nodes will be set to a unique Network ID and Join Key for this network They w...

Page 18: ...ode Discovery select the gateway from the tree and click the Node Discovery switch to move it in the opposite position CONFIGURE THE GATEWAY S MESH INTERFACE Select your SmartSwarm Gateway by clicking...

Page 19: ...e made up by you and is required for any MQTT connection Timeout Retry Interval and Keep Alive need to be filled in to work with any broker Defaults are shown below and should work in most instances T...

Page 20: ...rge as possible to save battery life and still get the measurement resolution required by the application The nodes are capable of a Measurement Interval of 10s to 84 600s 24 hours The default is set...

Page 21: ...ly send its data out of the gateway at specific time periods or when limits of an input are exceeded This is especially helpful in conserving data costs on a cellular network On Time Turning on On Tim...

Page 22: ...you want to start receiving data when an input exceeds a certain value or falls below a certain value Select which input on the node to which you would like to apply the rule Enter the Threshold valu...

Page 23: ...Wzzard Sensor Edge Nodes 23...

Page 24: ...l world Engineering units as it is published from the gateway Any consumers of the data could avoid having to make their own transformations In the Data Enrichment section enter the real world value b...

Page 25: ...ns received on the Digital Input at the node s Measurement Interval Rate A Rate Measurement Type will publish 1 the number of 0 to 1 transitions received on the Digital Input during a one second sampl...

Page 26: ...wireless traffic and battery life Digital outputs are Enabled by default The Inverter Switch defines if 1 High output or 1 Low output Inverter Off 1 High and 0 Low Inverter On 1 Low and 0 High The Di...

Page 27: ...UMIDITY INPUT CONFIGURATION Humidity inputs can be Enabled Disabled It s recommended that you disable all unused inputs to save on wireless traffic and battery life Humidity inputs are Enabled by defa...

Page 28: ...ovide a list of all nodes on the network with the same model number Select the MAC address of the node s you wish to copy to and click the Replicate Settings button All settings for the node and the I...

Page 29: ...walls Less than 300m outdoors with no obstructions 4 No node s data should have to go through more than 7 other nodes before reaching the gateway 8 hops is the maximum allowed by the network 5 It s be...

Page 30: ...tion review the nodes and their respective health color NODE LEVEL TROUBLESHOOTING There are two indications in SmartWorx Hub that a node is not behaving properly in the Mesh network 1 A node reports...

Page 31: ...nodes Nodes can also be added as repeaters Since all nodes act as repeaters just set one down and turn it on Is this node at the same height as others in the vicinity The farther from ground the node...

Page 32: ...y clicking the triangle next to the node in the tree Data is shown in the Engineering Units set in the I O point configuration The date and time of the last data read is shown at the top of the I O po...

Page 33: ...mounting ear flanges screws Certifications FCC FCC Part 15 Class A FCC Part 15 247 IC ICES 003 2016 ITE Emissions for Canada CE 2014 35 EU Low Voltage Directive 2014 53 EU Radio Equipment Directive 20...

Page 34: ...oups A B C D Safety IEC 60068 2 6 Sine Vibration 4G 10 500 Hz 0 06 in displacement IEC 60068 2 27 Mechanical Shock 50G 11ms 18 pulses Regulatory Approvals RoHS and WEEE Compliant THIONYL CHLORIDE LITH...

Page 35: ...ounting Mounting Mounting bracket included VHB adhesive strip included or ZIP ties not included Weight 0 09kg 0 2 lb Certifications FCC FCC Part 15 Class A FCC Part 15 247 IC Industry Canada RSS210 Re...

Page 36: ...ish interval Uses falling edge or rising edge based on Invert Enabled Setting Input Counter Channels Actively counts either falling edge Invert Enabled or rising edge Invert Disabled Can use a multipl...

Page 37: ...Clear Frequency 2405 5 k 11 MHz Modulation IEEE 802 15 4 Direct Sequence Spread Spectrum DSSS Raw Data Rate 250 kbps Range Indoor 100 m Outdoor 300 m Receiver Sensitivity Packet Data Error Rate PER 1...

Page 38: ...HANICAL DRAWINGS WZZARD INDUSTRIAL NODE MODELS Figure 1 Mechanical Drawing Wzzard Industrial Models Units millimeters inches WZZARD COMMERCIAL NODE MODELS Figure 2 Mechanical Drawing Wzzard Commercial...

Page 39: ...BB WSD2C21150 Wzzard Mesh Wireless Sensor Industrial Cooler HVAC Node Conduit _Sensor Inputs 2 Analog Inputs 1 Digital Input 1 Digital Output 2 Thermocouples 2 Thermistors 1 Internal Temperature Indo...

Page 40: ...Wzzard Sensor Edge Nodes 40 DECLARATION OF COMPLIANCE...

Page 41: ...Wzzard Sensor Edge Nodes 41...

Page 42: ...Wzzard Sensor Edge Nodes 42 DECLARATION OF CONFORMITY CE...

Page 43: ...Wzzard Sensor Edge Nodes 43...

Page 44: ...Wzzard Sensor Edge Nodes 44 ADVANTECH B B SMARTWORX TECHNICAL SUPPORT Phone 1 800 346 3119 Fax 1 815 433 5109 Email support advantech bb com Website www advantech bb com...