Electric connections: 

 

  CAUTION: before connecting the machine, make sure that the feeder is 
disconnected to the electrical network. 

The electric installation must be carried out by an experienced electrician and the 
supply must come from a severing equipment and differential protection; the whole 
must be carried out according to standards' in force in the country where the 
material is installed. 

  Characteristics of the electric supply: 
- 230 V +/- 10%, single-phase current, 50 Hz 
- Mode of neutral TT and TN.S; the circuit of heat pump must be connected to an 
earth circuit.   

 

 

 

 

 

 

 

 

 

Characteristic minimum of the protection:  
- Protection must be of 16 A, by circuit breaker or fuse; it must protect the Heat 
pump exclusively; the circuit breaker must be specified with curve D, the fuse must 
be specified Am. 
- Differential protection : 30 mA (the length of cable between the connector block of 
the heat pump and the protection of should not exceed 12 m). 

 
Control : 
 

The heat pump is fitted out with a water flow detector which function is to apply 

the signal to the electronic card when the water flow is sufficient. 
 

We  recommend  when  it  is  possible  to  control  the  heat  pump  to  the  filtration 

pump (by contacting relay non supplied to insert in the feeding circuit of the heat 
pump). 
 
 

The remmonded water flow speed is 3m

³

/h. 

 
 
Removed control panel: 
 

An extension cord allows the removal of the panel in inserting it in a standard 

electric box into the technical local; the option is supplied with a cover allowing to 
seal the aperture let by the removal of the control panel. 
 
 
 
 
 

 
 
 
 
 

14 

Summary of Contents for BP-50WS-C

Page 1: ...Directions for installation and maintenance...

Page 2: ...explored view Wire control operation General diagram of the refrigerating circuit Safety and control systems Electric diagram 5 Installation p12 Rules of installation Hydraulic connections Electric c...

Page 3: ...se not in conformity and random will be considered as dangerous and unsuitable The assembly the electric connection and the start up must be carried out by specialized and professional person When con...

Page 4: ...e complete state of the machine 4 Technical description Characteristics MODEL BP 50WS C Power supply 230V 50Hz Heating consumption power kW 0 9 Heating restored power kW 4 6 Heating nominal intensity...

Page 5: ...ntrol panel 5 Fast connection for water outlet 6 Refrigerant pressure manometer 7 Wire connection for power supply 8 Fast connection for water intlet 9 Evaporator 10 Fan 11 Compressor 12 High and low...

Page 6: ...6...

Page 7: ...unning press or to enter operation parameter check interface But can t change parameters Except the parameter 0 for water temperature setting If the heat pump is running the LED display shows current...

Page 8: ...ime displayed and ON to blink press TIMER ON botton again Change the hour using the and keys Press TIMER ON botton again to change the minutes using the and keys Press TIMER ON botton again the end Pr...

Page 9: ...ressure and in temperature by the compressor which sends it in the condenser exchanger where it loses its heat in giving it to the water of swimming pool and comes back in liquid state it loses its pr...

Page 10: ...ettings than this required With 4 safety systems A water flow detector placed at the exit of the exchanger A high pressure gas circuit breaker a low pressure gas circuit breaker An outlet compressor t...

Page 11: ...11 Electric diagram...

Page 12: ...place the fan would recycle its air and the Heat pump would be down performance The fan should not blow towards the windows or crossing point Safety distance between the swimming pool and the foot ba...

Page 13: ...nd connect the pipe if need Hydraulic connections To respect imperatively Connection is carried out with a by pass located on the circuit of filtration upstream appliances of the chemical treatment of...

Page 14: ...rotect the Heat pump exclusively the circuit breaker must be specified with curve D the fuse must be specified Am Differential protection 30 mA the length of cable between the connector block of the h...

Page 15: ...tion the swimming pool water into the pipes Engage the circuit breaker of pump of filtration Set the water temperature into the swimming pool adjustable from 15 C to 40 C The heat pump heats until the...

Page 16: ...at Pump in these conditions the totality of the water flow goes by the Heat Pump Put into service the Heat Pump in heating mode wait for the indicated pressure being stabilized the correct setting of...

Page 17: ...mes more electricity The temperature sensors compressor outlet and the magnetic circuit breaker on the compressor power supply protect the compressor from these extreme conditions the error messages E...

Page 18: ...he pressure switch Have Too much refrigerant gas present the heat pump checked by a refrigeration technician EE 02 Compressor and fan stopped Low pressure protection Not enough refrigerant gas Have th...

Reviews: