6-8
Operation with Field Communication software (CFS100)
Azbil Corporation
Model MTG11A/18A, MTG11B/18B, MTG14C
Measurement Range Configuration
This section explains how to configure the measurement range of the pressure
transmitter.
Select DEVICE SETUP
→
BASIC SETUP
→
Range Values.
LRV: Value at which 4 mA is output
URV: Value at which 20 mA is output
Double-clicking LRV or URV displays the settings screen. After configuring the
measurement range, close the edit screen and click the Send button to send the
measurement range value to the pressure transmitter. Values can be input to two
decimal places.
Note: In SFC and CommPad, when the LRV is changed, the URV also
changes by the same amount in order to keep SPAN unchanged. In Field
Communication Software Model CFS100, when LRV is changed, URV
does not change.